background image

Installation Guide

RE-DM6 

Radia Eclipse 6-Channel Dimmer Module (120 or 240 volts)

Overview

The RE-DM6 RADIA Eclipse 6-Channel Integrated Dimmer Module (120V: 

FG706-03

240V: 

FG706-04

) controls up to six circuits with six 1200-watt onboard dimmers 

(FIG. 1). The RE-DM6 is designed for use with the RDA series of enclosures, in an 
AMX Lighting™ modular digital dimming system. The RE-DM6 is controlled by AXLink 
or by dry (contact) closures.

Specifications

Suggested Installation Loads  

Caution: Pre-Installation Notes

WARNING

: This unit should be installed only by qualified electrical personnel, and in 

compliance with all national electrical codes, local codes and ordinances. To prevent 
possible personal injury or death, disconnect power to the enclosure 

at the breaker 

box 

before attempting to work with any AMX Lighting modules.

All Class 1 and 2 wiring must be connected to their dedicated terminals.

Class 1 wiring should be connected through the top of the enclosure, and Class 

2 wiring through the bottom.

Load conductors must be same size as line conductors, regardless of 

connected load.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times, and maintain 12” (30.48 cm) 

clearance around the top and bottom.

Test loads for shorts before connecting.

Class 2 wiring must be rated 300V or higher.

For indoor use only.

AC lighting loads only.

For more information, refer to the RE-DM6 instruction manual available at 

www.amx.com

.

Radia Lighting System Configuration Pages

The AMX Radia Web pages provide a simple interface for users of the Radia Duet 
module. The web pages reside on the AMX master when running the Radia Duet 
module and may be accessed through Internet Explorer or Mozilla Firefox. The RE-
DM6 may also be configured using NetLinx code or a terminal. For more information, 
refer to the RE-DM6 instruction manual available at 

www.amx.com

.

High-Voltage Connections

Each AMX Lighting module has its high-voltage connectors marked on its circuit 
board. Line, load, and neutrals are also clearly marked.

Line-in Connections

Using two feeds for Line 1 and Line 2 provides two 2400 W inputs.

Jumping Line 1 and Line 2 provides a single 2400 W input (FIG. 3).  

FIG. 1  

RE-DM6 6-channel Integrated Dimmer Module

RE-DM6 Specifications

Dimensions (HW):

5.75" x 10.0" (146.05 mm x 254.00 mm)

Weight:

4.5 lbs (2.04 kg)

Line input:

• 120, 240 VAC, single phase, 2W+G, 50/60 Hz, 2400 W,

 one feed

• 120, 120/240, 240 VAC, single phase, 3W+G, 50/60 Hz, 

4800 W, dual feed

Output:

• 1200 W max. per channel @120, 240 VAC
• 2400 W max. total, all 6 channels on with single 2400 W 

feed

• 4800 W max. total, all 6 channels on with dual 2400 W 

feeds

• Line input #1 goes to dimmer 1, 3, and 5; line input #2 

goes to dimmer 2, 4 and 6

• All electrical ratings are for continuous duty

Wire rating:

Use only copper wires rated at 75°C (167°F) min.

Torque terminals:

To 20 in-lbs (2.3 N/M)

Maximum wire size:

10 AWG (4 mm²)

Wire stripping length:

0.5" (13 mm)

AXLink Port:

4-pin 3.5mm green captive wire connector - AXLink 
communication signaling with 12VDC power in.

Aux Power:

2-pin 3.5mm green captive wire connector. This is a 12VDC 
power input that supplies additional power to the Radia PCB 
and connected Radia modules.

Dry Contacts:

• Emergency fire alarm relay connection - Closed relay 

activates preset 126. Other control is locked out until relay 

opens. Supports daisy chaining of up to 20 dimmers for 

this connection, with a maximum current requirement of 

200mA when daisy-chained.

• Failsafe connection - Works with a toggle switch - opening 

the switch triggers preset 128, closing the switch triggers 

preset 127. Supports daisy chaining of up to 20 dimmers 

for this connection with a maximum current requirement of 

200mA when daisy-chained.

BTU/hr:

300 single feed (2400 W); 600 dual feed (4800 W)

Mounting points

Power Devices

Jumper

Chokes

Neutral

High

Voltage

Connections

Ex12V

Aux Power

Mounting points

AXLink Address

DIP Switch

AXLink Connector

Dry Closures

Line In

Load Out

Class 1 wiring

Class 2 wiring

RE-DM6 Specifications (Cont.)

Idle current draw:

75 mA @ 120 VAC, 50 mA @ 240 VAC, 100 mA @ 13.5 
VDC

Certifications:

• FCC
• CE
• UL North America
• IEC-60950 Safety

Operating Temp 
Range:

0° to 40°C (32° to 104°F)

Included Accessories: • 2 4-pin captive 3.5mm wire connectors (

41-5047

)

• 4 #8-32x1/2” F-point mounting screws

Required Enclosures:

• RDA-ENC2 (

FG606-10

)

• RDA-ENC4 (

FG606-11

)

• RDA-ENC6/6B (

FG606-12/13/15

)

• RDA-ENC12B (

FG606-14/16

)

Dimmed

Switched

Incandescent

Motors

Neon, cold-cathode

Fans

FIG. 2  

High-voltage connections

FIG. 3  

Line-in Connections

Neutral

Load
Line in
Load

 

Dual 2400 W Inputs without jumper

Single 2400 W Input with jumper

Reviews: