NetLinx Programming
12
NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)
Channels
The PDU uses channels as specified in the following table.
Relay On/Off
: relay status
Temp Scale
: Off = C, On = F,
The PDU measures temperature with an accuracy of 1 degree C) via a remote temperature probe.
Temperature kept in non-volatile storage to retain across reboot.
Power Sense
: Signals that power (in watts) is above or below the specified trigger level (set via the
TRIGGER command).
SEND_COMMANDs (Cont.)
TRIGGER
Syntax:
TRIGGER-<outlet #>=<Power Sense Trigger>
Sets the Power Sense Trigger of the specified outlet to the specified value in tenths of
Watts.
Note
: A "Trigger" is a current level which will cause a power sense channel to activate if the
current exceeds the value.
?TRIGGER
Syntax:
?TRIGGER-<outlet #>
Responds with:
TRIGGER-<outlet #>=<Power Sense Trigger>
to report the trigger value in use on the outlet.
VER
Syntax:
VER
Responds with: Version (string) - example:
"Vx.xx"
ZAP!
Syntax:
ZAP!
Restores all settings on the PDU to factory default settings.
Unsupported options in responses are ignored / not reported.
Channel
Dev 1
Dev 2
Dev 3
Dev 4
Dev 5
Dev 6
Dev 7
Dev 8
1
Relay
On/Off
Relay
On/Off
Relay
On/Off
Relay
On/Off
Relay
On/Off
Relay
On/Off
Relay
On/Off
Relay
On/Off
2
Temp Scale
(off=C/on=F)
3
Ax 1
On/Off
Ax 2
On/Off
255
Power
Sense
Power
Sense
Power
Sense
Power
Sense
Power
Sense
Power
Sense
Power
Sense
Power
Sense
Summary of Contents for NXA-PDU-1508-08
Page 4: ...ii NXA PDU 1508 8 Power Distribution Unit 240V 10A Table of Contents ...
Page 8: ...NXA PDU 1508 8 4 NXA PDU 1508 8 Power Distribution Unit 240V 10A ...
Page 14: ...Installation 10 NXA PDU 1508 8 Power Distribution Unit 240V 10A ...
Page 18: ...NetLinx Programming 14 NXA PDU 1508 8 Power Distribution Unit 240V 10A ...
Page 19: ...NetLinx Programming 15 NXA PDU 1508 8 Power Distribution Unit 240V 10A ...