NetLinx Programming
11
NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)
NetLinx Programming
Device IDs
The NXA-PDU-1508-8 uses 8 AxLink device IDs, starting from the device ID denoted by the DIP switch:
Dev 1:
Output 1 + AxLink Power 1 + Input V Temperature
Dev 2:
Output 2 + AxLink Power 2
Dev 3-8:
Outputs 3-8
Supported SEND_COMMANDs
SEND_COMMANDs
PERSIST
Configures the designated power outlet to return to the last state on loss of power or reset of
the PDU.
By default, a shipping PDU shall have all power outlets PERSIST setting ON.
Syntax:
PERSIST-<outlet #>=<value>
Variables:
• <value> may be ON or OFF
• <outlet#> 1-8 for AC outlets, 9 and 10 for AxLink 1 and 2 bus power, respectively.
Note
: As there are limited write cycles to the storage of the persistent data, setting an outlet
to PERSIST ON should only be used when absolutely necessary, and never for very
frequent toggling operations.
?PERSIST
Queries the PERSIST state of all outlets.
Returns a comma-delimited list in the form:
PERSIST-1=<value>,2=<value>,3=<value>,4=<value>,5=<value>,
6=<value>,7=<value>,8=<value>,9=<value>,10=<value>
<value> will be 1 for ON or 0 for OFF, (e.g.):
PERSIST-1=1,2=0,3=0,4=0,5=0,6=0,7=0,8=0,9=1,10=0
?PHASEANGLE
Syntax:
?PHASEANGLE-<outlet #>
Responds with:
PHASEANGLE-<outlet #>=<Phase Angle>
Note
: "Phase angle" is the difference in phase between Voltage and Current, useful for
determining inductive vs. capacitive loading.
RESET
Syntax:
RESET
Triggers a
Power-On-Reset
of the PDU. A Power-On-Reset toggles all interruptible power
outlets.
?SERIAL
Syntax:
?SERIAL
Retrieves the 16-byte serial number assigned to the PDU.
Responds with:
SERIAL <XXXXXXXXXXXXXXXX>
where <XXXXXXXXXXXXXXXX> is the 16-byte serial number assigned to the unit.
Summary of Contents for NXA-PDU-1508-08
Page 4: ...ii NXA PDU 1508 8 Power Distribution Unit 240V 10A Table of Contents ...
Page 8: ...NXA PDU 1508 8 4 NXA PDU 1508 8 Power Distribution Unit 240V 10A ...
Page 14: ...Installation 10 NXA PDU 1508 8 Power Distribution Unit 240V 10A ...
Page 18: ...NetLinx Programming 14 NXA PDU 1508 8 Power Distribution Unit 240V 10A ...
Page 19: ...NetLinx Programming 15 NXA PDU 1508 8 Power Distribution Unit 240V 10A ...