background image

-9-

PROBLEM

POSSIBLE CAUSES

SOLUTION

No hot water

1. No power to unit

2. Circulator air-bound

3. Faulty circulator or zone valve

4. Faulty control

5. Boiler inoperable

1. Check circuit breaker, boiler emergency switch and boiler reset switch.

2. Purge air.  Ensure circulator is on Boiler Supply. Check air vents.

3. Check circulator and zone valve. Repair or replace if necessary.

4. Check continuity. Switching circuits should close. If not, replace control.

5. Check boiler system. Boiler must operate to generate hot water.

Insufficient hot water

1. Demand exceeds capacity

2. Temperature too low

3. Boiler lacks output for simultaneous heat & hot water

4. Fouled heat exchanger

5. Insufficient heat exchanger flow

1. Check sizing based on household size and boiler output.

2. Increase temperature setpoint.

3. Set up for priority.  If problem persists add storage or increase tank size.

4. Check Boiler Supply/Boiler Return during cold startup.  If difference is less 

than 20°F, clean heat exchanger as outlined below. Install water treatment 

equipment to prevent recurrence.

5. Check for undersized or faulty circulator, stuck or undersized zone valve. 

Ensure all shutoff valves are open.  Check for stuck flow check valve. Purge 

boiler loop to remove air.

Water too hot

1. Improper plumbing

2. Temperature set too high

3. Temperature sensor not fully inserted

4. Stuck zone valve

5. Flow check valve stuck open

1. If Boiler Return is plumbed to the suction-side of a heating circulator, over-

heating will occur when the home’s heat is on.  Fix plumbing.

2. Reduce temperature setting.

3. Re-insert temperature sensor.

4. Repair or replace.

5. Clean, repair or replace.

Relief valve dripping 

or opening

1. Thermal expansion tank undersized or missing

2. Thermal expansion tank set improperly

3. City pressure too high

4. System over temperature

5. Faulty relief valve

1. Install the properly sized thermal expansion tank.

2. Ensure precharge air pressure matches static water pressure.

3. Install a Pressure Reducing Valve (PRV) if city pressure is over 80 psi.

4. Determine cause of over temperature condition and correct problem.

5. Replace relief valve.

Discolored water  

at faucet

1. Poor water quality

2. Sediment or suspended particles

1. Have water tested for contaminants.

2. Install sediment filter, purge unit more often to avoid future problems.

Boiler will not operate 

when calling for  

hot water

1. Improper or loose wiring

2. Boiler high limit has been reached

3. Post Purge (POS) set too high

4. Problem with boiler system

1. Check connections against wiring diagrams in this manual.

2. Boiler will periodically cycle on and off during operation.

3. Post Purge shuts the boiler off prior to reaching domestic setpoint. If set too 

high, the boiler may not have enough energy to raise the water temperature 

to setpoint. Reduce POS or set to 0 if the problem persists.

5. Have boiler diagnosed for proper operation.

8. Startup Procedure

9. Troubleshooting

1. PURGE HEAT EXCHANGER:

 The heat exchanger should be free 

of large air pockets to allow the circulator to operate properly.  Using 

the diagram below as a guide, isolate the boiler return line and 

flush the loop until large air pockets are purged.  After this, the air 

elimination equipment will collect smaller air bubbles.

2. FILL TANK:

 Open the hot water fixture furthest from the heater.  

Open the cold water supply and allow the water to run until air stops 

emerging.  Air pockets may appear at any hot water fixture.  This is 

considered normal and will clear as hot water is used.

3. START HEATER:

 Turn power on to the unit. Digital Control models 

come pre-set to 120°F for safety. Mechanical controls should have 

the knob rotated to the 120°F mark. The circulator or zone valve 

should operate and the boiler should start.

4. CHECK OPERATION:

 The water heater will begin to heat.  

Depending upon the size of the water heater, output of the boiler 

and the space heating load, the unit should typically reach set 

temperature within 15 to 60 minutes.  If heating does not occur, 

consult the troubleshooting section in this manual.  

Note: 

Large 

heaters coupled with small boilers may exceed this time period 

upon initial startup.

5. SET TEMPERATURE:

 The control should be set to the minimum 

temperature consistent with the user’s needs. This maximizes 

efficiency and reduces scald potential.

6. The water heater and system should be periodically checked by a 

licensed professional at least annually and more often as system ages.

1. Close 

Return

3. 

Purge 

Air

2. Fill 

Boiler

Summary of Contents for HYDROMAX HM-41

Page 1: ...The heat transfer medium must be water or other nontoxic fluid having a toxicity rating or class of 1 as listed in Clinical Toxicology of Commercial Products 5th edition The pressure of the heat trans...

Page 2: ...t the same time the water heater may not be supplied with enough hot boiler water to recover adequately The delivery of domestic hot water will be diminished In many but not all cases this is not a pr...

Page 3: ...etaining Screws 2 Heat Trap Boiler Supply Hot Water Outlet 15 10 5 0 0 2 4 6 8 Head Loss Feet Flow Gallons Per Minute HYDROMAX Components Single Wall Shown Two Piece Cover Removal and Installation Hea...

Page 4: ...rwise penetrate the steel outer tank shell Do not screw pipe hangers or other hardware into the exterior of the tank BOILER PIPING 1 Plumb the circulator or zone valve on the BOILER SUPPLY line 2 Pipe...

Page 5: ...duit metal clad cable or raceways Power Limited Circuit Cable needed not be provided with the protection specified above if it is securely fastened to the appliance jacket and follows the contour of t...

Page 6: ...B C1 C2 L2 ORANGE ORANGE WHITE BLACK BLUE BLUE VIOLET VIOLET POWER BURNER PUMP PRIORITY HYDROMAX CIRCULATOR HEATING CIRCULATOR L1 B B2 Z W C1 C2 L2 Millivolt HYDROMAX CIRCULATOR HEATING CIRCULATOR ORA...

Page 7: ...capacity select appropriate size for proper operation Default is 41 Gallons 26 41 60 80 120 BTU Transfer Real time BTU transfer estimate in 1000 BTU Hr increments Diagnostic readout only 0 199MBH Hr A...

Page 8: ...l Gas Valves Non Priority AQUASTAT ZONE VALVE MOTOR 24VAC END SWITCH TRANSFORMER L1 L2 4 Wire AQUASTAT Boiler Control Input HYDROMAX CIRCULATOR OR ZONE VALVE DHW ZONE Boiler Controls Zone Valves Unive...

Page 9: ...faucet 1 Poor water quality 2 Sediment or suspended particles 1 Have water tested for contaminants 2 Install sediment filter purge unit more often to avoid future problems Boiler will not operate whe...

Page 10: ...obtained at the place of purchase Use proper safety equipment when installing EXPLOSION HAZARD The pressure of the heat transfer medium must be limited to a maximum of 30 psig by an approved safety or...

Page 11: ...ing Panel Mechanical Control 4 2704R498 2704R498 Ener G NET Digital Temperature Control 5 940R2 940R2 Temperature Sensor Thermistor 2704 259 2704 259 Mechanical Temperature Control 6 2704 093 2704 093...

Page 12: ...2015 AMTROL Inc Part 9040 694 11 15 1400 Division Road West Warwick RI 02893 USA T 800 426 8765 F 800 293 1519 www amtrol com...

Reviews: