-8-

Step 5 - Connect boiler supply pipe. Figure 1.

a.

Shut off the cold water supply valve to the boiler, and
drain it using a hose attached to the drain valve at the
boiler.

b.

When the boiler system piping is drained, cut the
piping to accommodate the supply line tee. Install the
tee between the boiler supply outlet and any system
zone valve or flow check.

c.

Connect the circulator flange and mount the
circulator to the boiler supply. 

Be sure the flow

arrow points towards the BOILER MATE™

. Mount

the second flange to the circulator.

d.

Connect a 3/4" NPTM to a 3/4" sweat adapter to the
second circulator flange.

e.

Using short lengths of tubing, connect the 3/4"shut-
off valve.

f.

Run the 3/4"copper tubing with necessary fittings to
the point of connection to the boiler supply tee.

Step 6 -  Connect boiler return pipe. Figure 1.

a.

Connect the 3/4" NPT, boiler return fitting and

connect the drain valve and union.

b.

Sweat a short length of tubing to the adapter and
connect the weighted check valve with the flow
towards the boiler (preventing flow towards the
BOILER MATE™). Failure to do so will result in the
BOILER MATE™ overheating.

c.

Run the 3/4" tubing and fittings as required to the
point of connection to the boiler return.

NOTE: This point must be between the boiler return
tapping and any system circulator(s). Failure to do so
will result in the BOILER MATE™ overheating.

Step 7 -  Refill the boiler system

a.

Open the cold water supply valve to the boiler.

b.

Check for system leaks.

c.

Close the weighted check valve on the boiler return
piping of the BOILER MATE™

d.

Open the drain valve on the boiler return line to
release entrapped system air.

e.

Close the drain valve 

f.

Open the weighted check valve.

C. ELECTRICAL WIRING

All wiring must be in accordance with local codes, regulations,
and ordinances or, in the absence of such codes, the National
Electrical Code ANSI/NFPA No. 70, latest edition.

The BOILER MATE™ thermostat can be used for either 24 or
120V AC. The thermostat is packaged separately and is installed
by sliding the capillary tube into the thermostat well.

Electrocution hazard. First
dis-connect

all electrical power

before doing any electrical work.

Electrocution hazard. The BOILER
MATE™ must be electrically
grounded.

Electrical supply must come from the
boiler side of boiler’s emergency
shut-off switch in order to prevent
unsafe boiler operation.

SEPARATE CIRCULATOR

I. BOILER MATE™ as Separate Zone - Non-Priority

A.

Use of separate BOILER MATE™ ZONE CIRCULATOR

Step 1 

- Disconnect electrical power.

a.

Turn off the boiler service switch.

b.

Turn off the safety switch (if separate from 
the service switch).

c.

Switch off the branch circuit breaker.

Step 2

- Remove electrical box cover on Thermostat.

Step 3

- Wire BOILER MATE™ using 

Schematic #1 or #2.

a.

Install BX connector.

b.

Insert outside wiring to BOILER MATE™
through electrical conduit opening on 
thermostat.

c.

Complete exterior electrical wiring per 
Schematic #1 or #2.

Step 4

- Turn boiler low-limit control (it is part of the 

boiler control) to the off position.

Note: 

Some boilers require minimum setting of low limit.

Step 5

- Adjust boiler high-limit control to the desired 

setting.  In  most cases 180° F to 200° F 
is acceptable.

Step 6 

- Re-assemble electrical box cover.

Step 7

- Re-connect electrical power.

B.

Use of only the heating system circulator.  

When wiring a separate zone valve, follow all steps in 1A

except for Step 3c. Use Schematic #3(A, B or C)
depending upon the type of zone valve. (Zone valve
sizing per pg. 5)

II. BOILER MATE™ - Priority Wiring

Hot Water Before Space Heating

A.

Use of separate BOILER MATE™ zone.
A DPDT relay is to be used. Refer to Schematic #4.

Step 1

- Disconnect electrical power.

a.

Turn off the boiler service switch.

b

. Turn off the safety switch (if separate from 

SEPARATE CIRCULATOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for BOILER MATE TD-41Z

Page 1: ...follow the required procedures as you use your BOILER MATE Return this booklet to its original envelope and keep it with the BOILER MATE This manual may become out of date by later amendments Check ou...

Page 2: ...R CLOSED HYDRONIC HEATING SYSTEMS 4 INSTALLATION Forced Hot Water Closed Hydronic Heating System 6 A General Installation Requirements 6 B Piping 7 C Electrical Wiring 8 D Post Installation and Start...

Page 3: ...PLUMBING FIXTURE WILL NOT RESULT IN A DRY BOILER IF THE BOILER CONTINUES TO FIRE AN EXPLOSION HAZARD EXISTS THIS UNIT MUST BE INSTALLED AS A SEPARATE HEATING ZONE DO NOT CONNECT THIS UNIT TO AN EXISTI...

Page 4: ...at the same time the BOILER MATE may not be supplied with enough hot boiler water to recover adequately The delivery of domestic hot water will be diminished In many but not all cases this is not a pr...

Page 5: ...REQUIRED IF a Back flow preventer check valve or pressure reducing valve is installed anywhere between the BOILER MATE and the city main As needed pipe dope or Teflon tape Do not forget an EXTROL and...

Page 6: ...ble Surfaces LEFT SIDE 10 REAR 1 RIGHT SIDE 10 FLOOR 0 TOP 30 FRONT 1 Recommended Clearance for Servicing LEFT 10 HEAD ROOM 30 RIGHT 10 REAR 1 FRONT 30 4 Instructions for reversing unit The unit is de...

Page 7: ...TRANSFER MEDIUM MUST BE LIMITED TO A MAXIMUM OF 30 PSIG BY AN APPROVED SAFETY OR RELIEF VALVE ON YOUR BOILER THE TANK PRESSURE MUST BE LIMITED TO 150 PSIG MAXIMUM BY THE INSTALLATION OF A TEMPERATURE...

Page 8: ...ions and ordinances or in the absence of such codes the National Electrical Code ANSI NFPA No 70 latest edition The BOILER MATE thermostat can be used for either 24 or 120V AC The thermostat is packag...

Page 9: ...the BOILER MATE If set too high the resulting hot water can cause painful scalding with possible serious and permanent injury The temperature at which this occurs varies with a person s age and the le...

Page 10: ...10...

Page 11: ...valve from the top of the BOILER MATE taking care to avoid contact with the hot water which may drain out of the lines leading to the domestic uses 5 Drain the BOILER MATE until the water within the t...

Page 12: ...THE ABSENCE OF LOCAL CODES WITH THE NATIONAL ELECTRIC CODE 2 HEAT EXCHANGER PACKAGE INCLUDE ITEMS 5 11 3 TORQUE NUTS 12 TO 14 FT LBS FAILURE TO USE THE CORRECT REPLACEMENT PARTS MAY MAKE YOUR UNIT UNS...

Page 13: ...filter strainer in steam boiler systems 2 Insufficient or runs out of 1 BOILER MATE 1 Set BOILER MATE hot water at faucet temperature setting too low temperature control to a higher setting 2 Undersiz...

Page 14: ...14 DATE SERVICE PERFORMED COMMENTS CONTRACTOR 9 SERVICE RECORD...

Page 15: ...d as described in the Manual provided with the Product to any failure or malfunction resulting from abuse including freezing improper or negligent handling shipping by anyone other than AMTROL storage...

Page 16: ...West Warwick Rhode Island 02893 Part 9040 628 REV B 7 04 16...

Reviews: