background image

-11-

The BOILER MATE™ is intended to provide a tank service life of
many years.  Components, however, may be subject to failures
that require service.  Failure to use the correct procedures or parts
in these circumstances may make the unit unsafe. 

• DO NOT OPEN DOWN-STREAM FIXTURE IF YOU

HAVE LOOSENED THE TOP CONNECTIONS.

• DO NOT OVER-DRAIN THE TANK - THE HEAT

EXCHANGER MUST REMAIN COVERED BY WATER TO
AVOID DAMAGE TO THE LINER.

The owner should arrange to have the following inspections

and simple maintenance procedures done at the
frequencies suggested.

a. Domestic Water Piping

- Yearly Visual Inspection Check

all piping for a signs of leakage at joints, unions and shut-
off valves.  Remedy as needed. 

b. Boiler Water Piping

- yearly Visual Inspection Check all

piping for signs of leakage at joints, unions and shut-off
valves. remedy as needed.

c. T & P Relief Valve 

- Yearly Inspection

d. Sediment 

- Monthly Inspection - depending on water

conditions
Depending on water conditions, a varying amount of
sediment may collect in the tank.  This is normal. Levels
requiring service are indicated by a small temperature
difference in the supply and return lines.  (See also "Scale"
below.)  Repeated flushing usually clears such material.  As
a preventive measure, each month water should be drawn
from the tank at the drain valve until it runs clear.

e. Scale

- Monthly Inspection

A small temperature difference between the water entering
and leaving the coil may indicate a scale build-up.  A water
softener will  prevent this problem.  (See also "Sediment"
above.)  Repeated flushing should also resolve the
problem.  If not, proceed as follows:

1.

To avoid water damage to nearby areas in subsequent
steps, shut off the cold water supply to the BOILER
MATE™.

2.

Make a note of the temperature control setting on the
BOILER MATE™, then turn the unit off by depressing
the key switch on the Smart Control™ until the unit
reads "OFF".

3.

Relieve the water pressure in the tank by opening a
hot water faucet.  This will reduce the risk of scalding
injury.

4.

Remove the relief valve from the top of the BOILER
MATE™, taking care to avoid contact with the hot
water which may drain out of the lines leading to the
domestic uses.

5.

Drain the BOILER MATE™ until the water within the

tank is even with the top of the heat exchanger -
roughly 15 gallons for 41-gallon units and 5 gallons for
26-gallon units.

Do not over-drain the tank.  Improper
thermostatic control could result

during Step 6 and lead to damage to the BOILER MATE™.

6.

Using a funnel, pour one gallon of commercial
phosphoric acid solution (commercial icemaker
cleaning solution) into the water tank through the top
opening.  Be sure that the manufacturer’s directions,
cautions, and warning on the container are followed:

7.

Set the temperature control to its highest setting and
operate the system until the control is satisfied.  

Note:

Boiler may cycle on its high limit several times during
this period. If the tank temperature setting has not
been satisfied after 45 minutes of boiler operation,
turn it to its lowest setting to stop boiler operation.

8.

Allow heated solution to set in tank for 30 minutes.
then drain tank completely using fitting and hose, as
required, to reach a floor drain.

9.

Fill water tank with fresh, cold, conditioned water and
drain completely at least two time to flush all
phosphoric acid mixture from the tank.

10.

Reinstall the temperature pressure relief valve, being

sure the (1) the temperature pressure relief valve
temperature probe reaches into the top portion of the
tank and (2) the top half union fitting is firmly in place.

11.

Open the cold water supply and fill the tank with

water. Then purge air from lines and tank by operating
hot and cold water faucets in the house.

12.

Return the Smart Control

to the setting noted in Step

2 and verify it is working properly as described on
page 17.

As an alternative to the above, the heat exchanger may be
removed from the BOILER MATE™, cleaned, and reinstalled (with
a new gasket); or, in some cases, a simple high velocity washing
by water from a wand may be used in place of Steps 5-9. The
chemical cleaning process, however, is the most effective if done
properly.

6. OPERATION/MAINTENANCE.

FOR FORCED HOT WATER, CLOSED HYDRONIC HEATING SYSTEMS

AND LOW PRESSURE STEAM BOILER.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for BOILER MATE TD-41Z

Page 1: ...follow the required procedures as you use your BOILER MATE Return this booklet to its original envelope and keep it with the BOILER MATE This manual may become out of date by later amendments Check ou...

Page 2: ...R CLOSED HYDRONIC HEATING SYSTEMS 4 INSTALLATION Forced Hot Water Closed Hydronic Heating System 6 A General Installation Requirements 6 B Piping 7 C Electrical Wiring 8 D Post Installation and Start...

Page 3: ...PLUMBING FIXTURE WILL NOT RESULT IN A DRY BOILER IF THE BOILER CONTINUES TO FIRE AN EXPLOSION HAZARD EXISTS THIS UNIT MUST BE INSTALLED AS A SEPARATE HEATING ZONE DO NOT CONNECT THIS UNIT TO AN EXISTI...

Page 4: ...at the same time the BOILER MATE may not be supplied with enough hot boiler water to recover adequately The delivery of domestic hot water will be diminished In many but not all cases this is not a pr...

Page 5: ...REQUIRED IF a Back flow preventer check valve or pressure reducing valve is installed anywhere between the BOILER MATE and the city main As needed pipe dope or Teflon tape Do not forget an EXTROL and...

Page 6: ...ble Surfaces LEFT SIDE 10 REAR 1 RIGHT SIDE 10 FLOOR 0 TOP 30 FRONT 1 Recommended Clearance for Servicing LEFT 10 HEAD ROOM 30 RIGHT 10 REAR 1 FRONT 30 4 Instructions for reversing unit The unit is de...

Page 7: ...TRANSFER MEDIUM MUST BE LIMITED TO A MAXIMUM OF 30 PSIG BY AN APPROVED SAFETY OR RELIEF VALVE ON YOUR BOILER THE TANK PRESSURE MUST BE LIMITED TO 150 PSIG MAXIMUM BY THE INSTALLATION OF A TEMPERATURE...

Page 8: ...ions and ordinances or in the absence of such codes the National Electrical Code ANSI NFPA No 70 latest edition The BOILER MATE thermostat can be used for either 24 or 120V AC The thermostat is packag...

Page 9: ...the BOILER MATE If set too high the resulting hot water can cause painful scalding with possible serious and permanent injury The temperature at which this occurs varies with a person s age and the le...

Page 10: ...10...

Page 11: ...valve from the top of the BOILER MATE taking care to avoid contact with the hot water which may drain out of the lines leading to the domestic uses 5 Drain the BOILER MATE until the water within the t...

Page 12: ...THE ABSENCE OF LOCAL CODES WITH THE NATIONAL ELECTRIC CODE 2 HEAT EXCHANGER PACKAGE INCLUDE ITEMS 5 11 3 TORQUE NUTS 12 TO 14 FT LBS FAILURE TO USE THE CORRECT REPLACEMENT PARTS MAY MAKE YOUR UNIT UNS...

Page 13: ...filter strainer in steam boiler systems 2 Insufficient or runs out of 1 BOILER MATE 1 Set BOILER MATE hot water at faucet temperature setting too low temperature control to a higher setting 2 Undersiz...

Page 14: ...14 DATE SERVICE PERFORMED COMMENTS CONTRACTOR 9 SERVICE RECORD...

Page 15: ...d as described in the Manual provided with the Product to any failure or malfunction resulting from abuse including freezing improper or negligent handling shipping by anyone other than AMTROL storage...

Page 16: ...West Warwick Rhode Island 02893 Part 9040 628 REV B 7 04 16...

Reviews: