NZ100 Installation Commissioning & Operation
Page 1
1.
INTRODUCTION
1.1
Unpacking and Inspection
Carefully check packing before unpacking goods for any transit damage. Unpack the goods and check
both externally and internally for any loose or damaged components that may affect the appearance,
installation or operation of the goods.
1.2
Anti Static Precautions
To prevent damage to panel components please ensure before touching or handling any of the wiring or
printed circuit boards within the panel that you are correctly earthed.
2.
SPECIFICATIONS
Size
220mmH x 290mmW x 80mmD
2.1
Power Supply/Battery Charger
Mains Supply
230V AC ± 10% @ 0.5A
Charger
Output Voltage
13.5V DC
Output Current
0.5A
Battery (one of only)
12V 7AH
System Quiescent Current
22mA
(After 10 minutes battery operation)
2.2
Outputs
Bell Circuits
(2 total)
Voltage
12V DC
Maximum current
3A max for both circuits
End of line resistor
10kOhm 1/4W 2%
Auxiliary output
Voltage
12V
Current
50mA max
2.3
Detector Circuit
Line voltage (open circuit)
22V
Short circuit current
22mA
Maximum Cable Length Impedance
100 ohm
End of line resistor
6.8kohm 1/4W 2%
Devices
Smoke detectors
24V
Electronic heat detectors
24V
Contact heat detectors
Manual call points