NZ100 Installation Commissioning & Operation
Page 6
4.
CONNECTING DEVICES
4.1
Detectors
A sample of the detectors approved for use with the NZ100 are listed below. ( See Appendix )
Detector Type
Iq
Circuit Limit
Order Code
Apollo Series 65 Ionisation Smoke Detector
45
µ
A
35
55000-217
Apollo Series 65 Photoelectric Smoke Detector
45
µ
A
35
55000-317
Apollo Orbis Photoelectric Smoke Detector with
Flashing LED
65
µ
A
24
201-0501
Thermal Detector Blue Indicating
40
µ
A
40
4255-0300
Thermal Detector Yellow Indicating
40
µ
A
40
4255-0400
Ampac Fireray Beam 2000
8mA
N/A
220-0004
Ampac Fireray Beam 50R
4
N/A
220-0005
Ampac Fireray Beam 100R
4
N/A
220-0006
Note:
Iq
=
Quiescent Current Draw
The maximum current on the Detector Circuit is 1.6mA, or 1600
µΑ
Rate of Rise Heat Detectors are also available.
FACP
+
-
6K8
EOL
1
2
SCREW
CAPS
MOUNTING
HOLES
WIRE IN
WIRE OUT
WIRE IN
TERMINATING METHOD
AMPAC
27.0
LED
MEASURE LINE VOLTAGE
WIRE OUT
UP TO 40 DETECTORS CAN BE
CONNECTED TO EACH CIRCUIT
NOTE:
T B 5
AMPAC
MANUAL CALL POINT
IN +
+ OUT
IN -
- OUT
SERIES
65 DETECTOR
L1 In
- R
L2
Earth
L1 Out
AMPAC HEAT
DETECTOR
Figure 4: Example of Detector & MCP Wiring
The zone circuit must be terminated with an end of line resistor with a value of 6.8K (2%
tolerance or better, power rating 1/4W)
4.2
Detector Limitations
1.
Most detectors, with the exception of thermostatic heat detectors, draw a small
monitoring current and this limits the number detectors that can be connected to a
given zone circuit. The total quiescent current of all devices on a zone circuit must be
less than 1.6mA @ 24V to ensure correct operation.
2.
Detectors are
not
intended for use in areas subject to higher than normal corrosive
environments or where hydrogen sulphide or other corrosive gasses may be present.
4.3
Manual Call Points
Type
Quiescent Current
Circuit Limit
Order Code
Ampac Manual Call Point
40µA
40
4255-0700