En-3
5. CHANGING THE ROOM TEMPERATURE CORRECTION VALUES
1
DIP switch on the printed circuit board inside the electronic control unit was set at the factory
for sensing the intake air into the indoor unit.
2
The following changes must be made to the settings of DIP switch if the unit is to be used
with the remote sensor (sensing the room temperature).
[For VRF Systems]
(When the model name of the indoor unit ends in “F” or “R”.)
3
Set DIP switches as follows.
SW1-3: OFF
SW1-4: ON
SW2-1: OFF
(When the model name of the indoor unit ends in “H”.)
3
Set up the functions as follows referring to Installation Manual of the indoor unit and the
remote controller or Design and Technical Manual.
Function Number “30” : Set Setting Number to “00” (Default)
Function Number “31” : Set Setting Number to “02”
[For Other Systems]
(Applicable only to “HEAT & COOL MODEL”)
3
Set DIP switch according to the height (L) of the remote sensor from the fl oor.
• Type
Ι
PCB
SW 1
SW 4
CN 8
SW 1
1
2
3
O
F
F
L
SW1-2
SW1-3
Correction Value
0 < L 1 m
(0 < L 39")
OFF
ON
SW 1
1
2
3
O
F
F
SW 1
1
2
3
O
F
F
0
1 m < L 2 m
(39" < L 79")
OFF
OFF
SW 1
1
2
3
O
F
F
SW 1
1
2
3
O
F
F
+2 °C
(+4 °F)
2 m < L
(79" < L)
ON
ON
SW 1
1
2
3
O
F
F
SW 1
1
2
3
O
F
F
+4 °C
(+8 °F)
• Type
ΙΙ
SW1
SW2
SW2
1
2
3
O
F
F
L
SW2-1
Correction Value
0 < L 2 m
(0 < L 79")
ON
SW 2
1
2
3
O
F
F
SW 2
1
2
3
O
F
F
0
2 m < L
(79" < L)
OFF
SW 2
1
2
3
O
F
F
SW 2
1
2
3
O
F
F
+4 °C
(+8 °F)
NOTE:
If the indoor unit model is “G”, it is not possible to
configure with DIP-SW. Perform room temperature
correction for both of cooling and heating with the
“FUNCTION SETTING” of Installation Manual of the
indoor unit.
Indoor unit model
AR
Y
G
54
L
H
T
A
TYPE
DESTI-
NATION
MODEL
MODEL
CODE
FUNC-
TION
MODEL
CHANGE
CODE
MADE IN
ORIGIN
SERIES
NAME
L
Function Number
Setting Value
0 < L 1.5 m
(0 < L 59")
30
02
31
03
1.5 m < L (59" < L)
Setting is not required
• Type
ΙΙΙ
Perform room temperature correction for both of cooling and heating with the “FUNCTION SETTING” of remote controller
to the models the PCB (Printed Circuit Board) described in Type
ΙΙΙ
of preceding paragraph “4.WIRING TO AIR-CONDI-
TIONER” is used.
L
Function Number
Setting Value
0 < L 1.5 m
(0 < L 59")
30
31
01
1.5 m < L (59" < L)
Setting is not required
L
Wall
Remote
sensor
Floor
9366394068-02_IM.indb 3
9366394068-02_IM.indb 3
4/19/2012 1:47:56 PM
4/19/2012 1:47:56 PM