30
Z-tron IV
TM
Point Level Control
Section 6:
Specifications
Power Requirements:
AC Units - Field Selectable:
95-145 VAC, 50/60 Hz, 2 Watt
215-265 VAC, 50/60 Hz, 2 Watt
DC Units:
24 VDC Unit: 19-29 VDC input, 2 Watt
Sensitivity:
0.3pF or less
Operating Point Range:
0 - 80 pF (20 Turn Pot / 4 pF per Turn)
Extended range with external pad capacitor, Pad ratio 1:1
Load Resistance:
Center to Ground, 1500 Ohms
Center to Shield, 750 Ohms
Shield to Ground, 750 Ohms
Failsafe:
Field adjustable to either High-Level Fail-Safe (HLFS)
or
Low-Level Fail-Safe (LLFS)
Output:
DPDT relay closure
Contact Rating:
5A @ 120 Vac non-inductive
2A @ 230 Vac non-inductive
Ambient Temperature:
-40°F to 145°F (-40°C to 63°C)
Temperature Effect:
0.5pF/50°F
Line Voltage Effect:
0.2pF/20V @ 120 Vac
Stability:
0.15pF/6 mo. maximum shift
Spark Protection:
100 Amp
Mounting: (Probe Dependant)
¾-inch NPT (Typical)