Digital Inputs
There can be between 16 and 160 digital inputs. These are normally used for monitoring the
operation of protection relays and switchgear via auxiliary contacts.
The digital inputs must have a DC power supply connected externally and the voltage must
be as specified in the System Drawings in Appendix V. When the contact being monitored is
closed, approximately 3 mA DC will flow through the contact.
On the analogue cards each group of 4 inputs is isolated from each other group and has a
common connection (marked C) for the field control voltage (FCV). This common
connection may be wired to either the battery positive or negative terminal. On the digital-
only cards there are 16 inputs arranged in isolated groups of 4, and there are 16 inputs
individually isolated. The normal state of the input is defined in the recorder configuration in
Display Station. The signal is displayed as being in the “Normal” or “Alarm” state.
Status Output Connections
The four status relay output circuits are available on the 16-terminal orange connector at the
right of the rear panel. The relays outputs are normally open, dry contacts in the shelf
(unpowered) state. The functions of these relays are described in the previous chapter.
Summary of Contents for TR-2100
Page 2: ......
Page 6: ...iv ...
Page 10: ...TR 2100 User Manual 4 ...
Page 16: ...TR 2100 User Manual 10 ...
Page 24: ...TR 2100 User Manual 18 ...
Page 34: ...TR 2100 User Manual 28 ...
Page 38: ...TR 2100 User Manual 32 ...
Page 54: ...TR 2100 User Manual 48 Figure 12 Analogue Input Board Jumpers ...
Page 78: ...TR 2100 User Manual 72 ...
Page 94: ...TR 2100 User Manual 88 ...
Page 98: ...TR 2100 User Manual 92 ...
Page 99: ...TR 2100 User Manual 93 Appendix V System Drawings ...
Page 100: ...TR 2100 User Manual 94 ...
Page 101: ......
Page 102: ......
Page 103: ......
Page 104: ......