User Manual
_________________________________________________________________
fdfefd fd
© 2019 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com 25
2) Battery Test
This item will test the performance of the battery. This item will be displayed under all UPS modes. However, the
battery test cannot be executed if the UPS is in Battery/Fault mode (a reminder will pop up in the screen). When
the battery test is selected, the screen will return back to the home page with “Battery Test Mode” displayed on the
top line. If the test is completed, the displayed status will change back to the current mode of the UPS.
Control:
Batt Test Mode
Turn On Batt Test?
Batt Test IP: 208.0V / 50.0Hz
Mute Yes OP: 208.0V / 50.0 Hz
Para Unlock No Batt: 245.0V / 50%
Load:
0%
Backup Time:
10H
3) Mute
This item will mute the buzzer. This item will be displayed under all UPS modes. However, the buzzer can be
muted only when the UPS is in battery/bypass/fault mode (a reminder will pop up in the screen). After the selec-
tion is confirmed, the display will return back to the home page and the mute icon will be displayed.
Control:
Battery Mode
Turn On Mute?
Batt Test IP: 0.0V / 0.0Hz
Mute Yes OP: 208.0V / 50.0 Hz
Para Unlock No Batt: 245.0V / 50%
Load:
100%
Backup Time: 10H
4) Para Unlock (part numbers with parallel option only)
This item allows the UPS to startup with parallel function and only appears when the LCD shows the warning of
“3F: Para Protect”. The warning means that the parallel system is in protection and could not start up because of
parallel communication failure. Before the parallel system is restarted, please confirm this selection first.
NOTE: Before executing this action, please check that the system cables and connections are connected correctly
and safely. Please read the related contents in the section under troubleshooting.
Control:
Is single or
Bypass Mode
Turn On
parallel cable OK?
Parallel: Master
Batt Test
IP:
0.0V / 0.0Hz
Mute
Yes
OP: 208.0V / 50.0 Hz
Para Unlock
No
Batt:
273.0V / 99%
Load:
0%