Interface
Description
Others :
Hot Standby
Backup Time
Backup Time :
Batt Groups :
1
Batt Cap :
9AH
Factor :
1.0
Backup Time Parameter Setting : (Authorized Installation
Personnel Only)
Batt Groups :
Set the number of battery groups ranging from
1 to 6. The default value is 1 group.
Batt Cap :
Set the battery capacity such as 7AH, 9AH, 10AH,
12AH, 17AH, 26AH, 40AH, 65AH, 100AH and so on. The
default value is 9AH.
Factor :
Calibrate the displayed backup time by adjusting this
multiplier factor. The formulation is listed below :
Displayed backup time = Original backup time X Multiplier
factor
The value of the default factor is 1.0 and can range from 0.5 to 2.
These parameters are for the battery backup time calculation.
3-7-2-6 . Alarm page
Alarm Info
Fault :
14 : Output Short
Warning :
01 : Bat Open
This page records and displays the faults and warning events as they occurred in time.