37
User Manual
_________________________________________________________
© 2020 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com
Warning
Icon
(Flashing)
Alarm
EPO enable
Beeping every second
Fan failure/Over
tempera- ture
Beeping every second
Charger failure
Beeping every second
I/P fuse broken
Beeping every second
Overload 3 times in 30min
Beeping every second
8.2 Warning Code
Warnin
g
Cod
e
Warning Event
Warning
Code
Warning Event
0
1
Battery unconnected
10
L1 IP fuse broken
0
7
Over charge
33
Locked in bypass after
overload 3 times in 30min
0
8
Low battery
3A
Cover of maintain switch is
open
0
9
Overload
3D
Bypass unstable
0
A
Fan failure
3E
Boot loader is missing
0
B
EPO enable
42
Over-temperature on
transformer
0
D
Over temperature
0
E
Charger failure