36
User Manual
_________________________________________________________
© 2020 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com
8.0 FAULT CODE
Fault Event
Fault
Code
Icon
Fault Event
Fault
Code
Icon
Bus start failure
01
None
Battery SCR short
circuited
21
None
Bus over
02
None
Inverter relay short
circuited
24
None
Bus under
03
None
Charger short circuited
2a
None
Bus unbalance
04
None
Can communication
fault
31
None
Inverter soft start failure
11
None
Over temperature
41
None
High Inverter voltage
12
None
CPU communication
failure
42
None
Low Inverter voltage
13
None
Overload
43
Inverter output short
circuited
14
Battery turn-on failure
6A
None
Negative power fault
1A
None
PFC current failure in
battery mode
6B
None
Inverter over current
60
None
Bus voltage changes
too fast
6C
None
Inverter waveform
abnormal
63
SPS 12V abnormal
6E
None
Inverter current detec-
tion error
6D
None
Transformer over tem-
perature
77
None
8.1 Warning Indicator
Warning
Icon
(Flashing)
Alarm
Overload
Beeping twice every second
Battery Unconnected
Beeping every second
Over charge
Beeping every second