28
User Manual
_________________________________________________________
© 2020 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com
03: Voltage Range for Bypass
Interface
Setting
Parameter 1 & 2:
Setting acceptable voltage range
for bypass mode. Set up the range by setting high and low
points. When it shows
“LLS” in parameter 2, please
press
“Enter” key and it will show “LS” in parameter
1. Now the low point in parameter 2 can be set up by
pressing
“Up” or “Down” key.
LS:
Set the acceptable low voltage for bypass. Setting
range is from 110V to 209V and the default value is
110V.
Pressing
“Enter” key to confirm the setting value for
low point. Then, it will show HS in parameter 1. Please set
up high point in parameter 2 by pressing
“Up” or
“Down” key.
HS:
Set the acceptable high voltage for bypass. Setting
range is from 231V to 276V and the default value is
264V.
04: Frequency Range for Bypass
Interface
Setting
Parameter 1 & 2:
Setting acceptable frequency range for
bypass mode. Set up the range by setting high and low points.
When it shows
“LLS” in parameter 2, please press “Enter”
key and it will show
“LS” in parameter
1. Now the low point in parameter 2 can be set up by
pressing
“Up” or “Down” key.
LS:
Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Pressing
“Enter” key to confirm the setting value for low
point. Then, it will show HS in parameter 1. Set up high point in
parameter 2 by pressing
“Up” or “Down” key.
HS:
Set the acceptable high frequency for bypass. 50
Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz. The default
value is 54.0Hz/64.0Hz.