Cable lengths must not exceed twenty-five (25) feet. For lengths greater than 25 feet, calculate
the voltage drop from the following formula:
2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP
Load Current
Wire Gauge (US)
Circular Mils
(kcmils)
Metric (mm2)
65 AMPS
6 AWG
26.24
13.3
130 AMPS
4 AWG
41.74
21.1
Table 3-2: Suggested Output Wiring Sizes *
Note: Use high temperature rated wire. Always consult the National Electrical Code
and/or local code regulations for proper rating and size of wire cabling prior to
installation.