BLU
25°C
17°C
33°C
ROSSO
20°C
12°C
28°C
19
GB
COMMANDS:
Ventilation is only allowed with the finning open, it is
necessary to open it manually.
The closure of the finning provokes the turning off of
the fan by the electronic thermostat remains active
and continuously records the environmental data for a
prompt restart when the finning opens again.
T
urning on/off
OFF The fan coil is off.
It may however start again in Heating mode
(Antifreeze function) if the room temperature falls to
below 7°C and the water temperature is suitable, in
this case the red Led flashes.
To start the fan coil, turn the knob towards the func-
tioning mode required in the AUTO position or in one
of the three ventilation speeds.
Speed selection
AUTO
The thermostat maintains the set temperature
changing the fan speed in Automatic Mode in accor-
dance with the room temperature and the set tempera-
ture.
The thermostat maintains the set temperatu-
re through cycles of coming on and off by
respectively using the minimum, medium or maxi-
mum fan speeds respectively.
Temperature selection
P
ermits the required temperature to be set.
The temperature corresponding with the selector set
at the central position depends on the active functio-
ning mode (Hot 20°C, Cold 25°C).
The differences of minimum and maximum tempera-
ture with respect to the central position are +8°C and
-8°C
Season change
The OMNIA HL PC - HL PCM fancoil automatically sets
the functioning at Hot or Cold in accordance with the
temperature of the water in the system.
Led (C) changes colour to indicate the operational
mode that is active:
RED On
indicates Heating operation
(heating).
Flashing
indicates antifreeze mode.
BLUE
On
indicates Cooling operation
(cooling).
FUCHSIA Flashing
indicates that the water in the
system has not yet reached the temperature
suitable for enabling the ventilation.
Led (D) indicates the activation of the
PLASMACLUSTER purifying system:
YELLOW On
indicates that the thermostat has detec-
ted a room temperature that requires the ven-
tilation to cut in a the same time as the venti-
lation the PLASMACUTTER is activated.
Fast flashing
indicates that the water circui-
ting in the system has not yet reached the
temperature required for enabling the venti-
lation, the PLASMACLUSTER is deactivated.
Off
indicates that the finning is closed and
that the fan cannot start. The PLASMACLU-
STER is off.
If the finning is open, Led (D) off indicates that
the thermostat is in stand-by mode (selector A
is in the OFF position) or that the thermostat
does not require the functioning of the fan.
Fast flashing
indicates a functioning fault of the
of the ambient probe (Emergency mode).
LIT INDICATORS
USE (OMNIA HL PC - HL PCM)
RED
BLUE
Summary of Contents for Omnia HL PC
Page 2: ......
Page 15: ...15 SCHEMI DI MONTAGGIO L N OMNIA HL PC HL PCM I...
Page 27: ...L N 27 INSTALLATION DIAGRAMS OMNIA HL PC HL PCM GB...
Page 39: ...L N 39 SCH MAS DE MONTAGE OMNIA HL PC HL PCM F...
Page 51: ...L N 51 EINBAUPL NE OMNIA HL PC HL PCM D...
Page 63: ...L N 63 ESQUEMAS DE MONTAJE OMNIA HL PC HL PCM E...
Page 67: ......