OPERATING MANUAL FOR HEATSAN   

98-0177A 

  Page 8 

5 CONTROLLER STANDARD SETPOINTS 

SETPOINT 

DESCRIPTION 

RANGE 

FACTORY 
SETTING 

%Rej 

The 2

nd

 TDS/Conductivity cell is used to 

monitor feed water.  Programming this 
setpoint to 1 allows the % rejection to be 
displayed. 

0-1 

C2 Limit 

When this value is met or exceeded, the 
alarm lamp will light and high TDS/Cond will 
show on the display.  To disable, set to 0. 

0-1 

C2 Range^^ 

Selects the range of inlet TDS/Conductivity 
monitor;  0 = 50, 1 = 100, 2= 250, 3= 500,  
4 = 1000, 5 = 2500, 6 = 5000. 

0-6 

Direct Feed 

This will change the behaviour of the device 
to allow it to be paired with a Heatsan 
disinfection system.  1 = direct feed with 
heatsan, 2 = standard RO. 

0-1 

TDS/Cond 
Range^^ 

Selects the range of TDS/Conductivity 
monitor;  0 = 50, 1 = 100, 2= 250, 3= 500,  
4 = 1000, 5 = 2500, 6 = 5000. 

0-6 

TDS/Cond 
UOM^^ 

Selects display of water quality in either µS 
or PPM.  0 = µS, 1 = PPM 

0-1 

Switch Select 

Selects if the switch inputs are normally open 
or normally closed. 

0-32 

Temp UOM 

Selects display of the temperature in either 
°F or °C.  0 = °F, 1 = °C. 

0-1 

Temp Offset 

Allows adjustment of the temperature 
reading by +/- 5 degrees. 

+/- 5 

Current Hours 

Current number of hours of RO system 
operation. 

0-6500 
hours 

Maximum Hours 

If the current operating hours exceed this 
limit, the operating hours warning will occur.  
To disable, set to 0. 

0-65000 
hours 

Flush Mode 

Selects if the inlet and RO pump relays 
operate during flush. 

1-4 

Flush Interval 

The interval between flush cycles.  Only valid 
with operation hour, elapsed time or off flush 
cycles. 

0-99 minutes

Flush Time 

The length of time a membrane flush cycle 
will last when flush is active. 

0-99 minutes

Flush Type 

Selects the type of flush.  Set to 0 to disable. 

0-8 

Tank Lo Restart 

Not used. 

N/A 

N/A 

^^Changing any setpoints indicated by this symbol will require the unit to be 
recalibrated and may require the range components be changed. 

Summary of Contents for 98-0177A

Page 1: ...OPERATION MANUAL FOR MRO CONTROLLER UPGRADE TO HEATSAN 98 0177A UPGRADE AN MRO FOR USE WITH HEATSAN 98 0177A 02 16 2015...

Page 2: ...OPERATING MANUAL FOR HEATSAN 98 0177A...

Page 3: ...OPERATION MANUAL FOR HEATSAN 98 0177A Page 3 CONTENTS PAGE 1 DOCUMENT HISTORY 1 2 CONTACT DETAILS 1 3 PREPARATION 2 4 CONTROLLER OPERATION 4 5 CONTROLLER STANDARD SETPOINTS 8...

Page 4: ...ription of Change A 17 02 15 Initial Release 2 CONTACT DETAILS For all service spares and consumables enquiries contact AmeriWater 1303 Stanley Ave Dayton Ohio 45404 Tel No 800 535 5585 Or your local...

Page 5: ...upgrade is complete Loosen the 2 retaining screws on the front of the control panel to gain access to the CPU Gently pry the CPU out of the socket being careful not to break any of the pins Discard t...

Page 6: ...o place Ensure that the chip is fully seated in the socket Return all power to the device Move the write protect jumper to the OFF position Power on the RO and access the program screen labelled as DI...

Page 7: ...mp starts OPERATING The RO unit is operating TANK FULL The unit is shut down due to a tank full condition TANK FULL 99 The unit is shut down due to a tank full condition If the number is blinking the...

Page 8: ...the switch is connected to the tank full high input When this switch has been active for 5 seconds the unit will shut down on tank full TANK FULL will show on the display When the tank full condition...

Page 9: ...s active for the delay programmed in the PF Delay Setpoint the unit will shut down for a pressure fault The display will show PRESS FAULT the alarm lamp will flash and the audible alarm will sound The...

Page 10: ...is warning will clear when the Conductivity drops below the Setpoint When the High Conductivity warning message is active the MRO will divert the PRODUCT WATER to drain through the Reject hose until t...

Page 11: ...ty in either S or PPM 0 S 1 PPM 0 1 0 Switch Select Selects if the switch inputs are normally open or normally closed 0 32 0 Temp UOM Selects display of the temperature in either F or C 0 F 1 C 0 1 0...

Page 12: ...inutes 3 Auto Reset When a pressure fault shut down is active the system will attempt to restart after this delay If set to 0 the system must be manually reset 0 99 minutes 0 Press Fault Delay The tim...

Reviews: