OPERATING MANUAL FOR HEATSAN
98-0177A
Page 9
SETPOINT
DESCRIPTION
RANGE
FACTORY
SETTING
TFO Time
The amount of time that a tank full override
lasts.
0-15 minutes
3
TF Restart
Selects whether the tank full restart delay is
in seconds or minutes. 0= seconds,
1=minutes.
0-1
0
TF Restart Delay When a tank full condition clears, the system
will restart after this delay.
0-99
seconds /
minutes
5
Alarm Silence
If the audible alarm is silenced, after this
delay, the alarm will resound. If this is set to
0, the alarm will remain silenced.
0-99 minutes
3
Auto Reset
When a pressure fault shut down is active,
the system will attempt to restart after this
delay. If set to 0, the system must be
manually reset.
0-99 minutes
0
Press Fault
Delay
The time a pressure fault must be active
before a pressure fault shut down occurs.
0-99
seconds
10
RO Start Delay
The amount of time between the inlet valve
opening and the RO pump start.
0-99
seconds
10
TDS/Cond Delay When the limit Setpoint is exceeded, no
alarm will be given until this time has expired.
0-999
seconds
10
TDS/Cond Limit
When this value is met or exceeded, the
alarm lamp wil light and high TDS/Cond will
show on the display. To disable, set to 0.
0-999
µS or PPM*
Based on
Water
analysis
* µS = microsiemens; PPM = Parts Per Million