American Standard YK-IOM-2 Installation Operation & Maintenance Download Page 20

20

Power-up  Initialization

The “initialization” by the Unitary Control Processor (UCP) oc-
curs each time the system is powered-up. The UCP performs
internal self-diagnostics checks, which include identifying the
equipment components of its system, and the configuring of it-
self to that system. It also checks itself to be sure it is function-
ing correctly. On units with the optional economizer, the
damper is driven open for 15-20 seconds and then fully closed
for 90 seconds. The UCP system indicator LED is turned to
“ON” within one second of start-up if operation is correct.

The Unitary Control Processor (UCP) switches are factory set
to provide comfort for most applications. Control cycles may
be adjusted as indicated in the table below. These switches
function similar to the heat anticipator adjustment in conven-
tional thermostats.

Unitary Control Processor (UCP)

Switch Settings for Cycle Timing

Switch 1

Switch 2 Cycle Time

OFF

OFF

NORMAL  (Factory Setting)

OFF

ON

LONGER

ON

OFF

SHORTER

ON

ON

*SPECIAL

*  Special applications, where very short cycles are

necessary to prevent excessive temperature swings.

Starting the Unit in the Heating Mode

Note: See “Sequence of operation” in the unit Service
Facts for a complete description of heating operating
sequence.

Check to ensure all grilles and registers are open and all unit
access doors are closed before start-up.

Purge the gas supply line of air by opening the union ahead of
the unit. When the odor of gas is detected, re-tighten union
and wait 5 minutes before proceeding.

Place the zone system switch in the heat position.

Postition the heating setpoint approximately 6

o

C (10

o

F) de-

grees above room temperature and place the fan switch in
"Auto" or "On" position.

Open the main gas valve and turn on unit main power supply.

Note: To bypass time delays, and verify the operation
of this unit from the roof, use the “Test mode
procedure” on page 3  and 4 of this manual.

The combustion blower motor and ignitor should energize.
The main burners should light within one minute from the time
the combustion blower starts. Initial start may be delayed
somewhat if unit is not purged and air is trapped in gas line.

If burners fail to ignite after 3 tries the ignition system will lock-
out. Reset by disconnecting and re-applying unit power.

Unit will start in the high fire mode. After a short run cycle it will
switch to low fire.

Note:  Blue smoke produced by the heat exchanger
during the initial burner firing is caused by a thin film
of oil on the surface of the heat exchanger. This oil
will burn off quickly.

Check control operation and burner operating conditions
through the sight glass in burner assembly cover.

Manifold Pressure

Connect a manometer to the pressure tap at the outlet side of
the unit gas valve. Read the manifold pressure with the main
burners firing. The manifold pressure reading indicated should
be a (negative) -50 Pa (2 inches of water column.)

If the manifold pressure reading does not match the value indi-
cated on the unit nameplate, the unit pressure regulator must
be adjusted as follows:

Remove the cover screw on the gas regulator (located on the
top side of the unit gas valve).

Turn the adjusting screw clockwise to increase manifold pres-
sure, or counter-clockwise to decrease manifold pressure.

 Open and lock unit

disconnect switch before continuing installation.
Failure to do so could result in severe personal injury
or death due to electrical shock or contact with
moving parts.

Adjust the evaporator fan motor rpm (at the motor sheave) to
a speed which most closely approximates the rpm value found
in the motor sheave/fan speed (rpm) table in the Service
Facts. To insure proper unit operation, the resulting airflow
must be or - 20 percent of the nominal airflow rate.

After adjusting the evaporator fan, check heat exchanger tem-
perature rise during furnace operation to insure that it falls
within the range specified on the unit nameplate.

If the temperature rise noted is outside of the specified limits,
adjust the fan motor sheave to cause the temperature rise of
the heat exchanger to fall within the required range.

Heating Shut-down

To exit the test mode, disconnect unit power for 3-5 seconds
and reapply. When running the unit using the zone sensor as
the control, position the selector switch at "Off". There will be a
delay of 0 - 90 seconds before the unit shuts down in this set-
ting.

 Do not operate the unit

without the evaporator fan access panel in place.
Reinstall the access panel after performing any
maintenance procedures on the fan. Operating the
unit without the access panel properly installed may
result in severe personal injury or death.

Summary of Contents for YK-IOM-2

Page 1: ...ould be done by qualified experienced technicians American Standard Inc 2000 Voyager TM Packaged Gas Electric 085 thru 250 Units INSTALLATION OPERATION MAINTENANCE Customer Property Contains wiring se...

Page 2: ...nstallation 14 Evaporator Fan Adjustment 14 Compressors 16 Pre Start Quick Check List 19 Power up Initialization 20 Unitary Control Processor UCP 20 Manifold Pressure 20 Final Installation Checklist 2...

Page 3: ...perature sensing function to the UCP Ignition Control Module There are two LED s located in the Ignition Control Module that monitor the operating status of the heater during the vari ous operating st...

Page 4: ...and control will revert to the zone sensor To terminate the test mode cycle the unit power at the unit disconnect Resistance Test Mode The resistance test mode is initiated by applying the appropri a...

Page 5: ...r Horizontal HORIZONTAL UNIT SI mm REAR VIEW SHOWING DUCT OPENINGS FOR HORIZONTAL AIR FLOW UNITS A B C D E F YK 085C 100C 406 413 510 76 162 914 YK 100B 125C 571 457 437 51 100 1053 YK 155B 175C 673 4...

Page 6: ...59 1509 2267 51 357 25 205 1205 1A YK 155B 175C 1692 1600 46 530 435 724 2588 1702 2597 51 357 25 191 1410 1A YK 200B 250B 2048 1956 46 565 591 725 2969 2057 2977 51 357 25 191 1765 Figure 1B Curb Dim...

Page 7: ...low or Horizontal Note Corner weights are given for information only Unit is to be supported continuously by curb or equivalent frame support Unit Support If unit is to be roof mounted check building...

Page 8: ...o closer than two feet from the unit to minimize noise and resistance Attaching Horizontal Ductwork to Unit All conditioned air ductwork should be insulated to mini mize heating and cooling duct losse...

Page 9: ...e K5 relay The burner fan then switches into high speed and the heating capacity is raised to maximum When the temperature of the zone has reached the setpoint the UCP de engerizes the relays K5 K6 H...

Page 10: ...10 Figure 5 Figure 6 Detail of the Gas Section...

Page 11: ...h due to electrical shock or contact with moving parts Measure the negative pressure downstream of the gas unit Connect a flexible hose to the gas unit branch connection and connect as electronic pres...

Page 12: ...onditioner 50 Hz EEC Voyager G20 41 4 92 49 1 91 70 6 90 77 4 91 G25 35 0 92 38 3 89 59 4 88 60 3 90 G31 37 7 92 48 6 90 57 3 88 78 2 92 YK 063CD X YK 073CD X YK 073DD X YK 085CD X YK 089CD X YK 100CD...

Page 13: ...Gas Flow 15 C 1013 mbar m3 h 4 7 5 3 8 3 8 2 Heat Rate kW 38 0 43 0 67 4 67 0 Reduce Rate Gas Flow 15 C 1013 mbar m3 h 4 5 4 9 7 8 7 9 Heat Rate kW 36 5 40 0 63 4 64 0 Natural Gas G31 30 37ou 50 mbar...

Page 14: ...AND ADJUSTED IF REQUIRED TO A NEGATIVE 50Pa 0 2 OF WATER COLUMN NEVER ADJUST THE REGULATOR TO A POSITIVE PRESSURE Manifold Pressure The unit manifold pressure regulator located on the gas valve is fa...

Page 15: ...cor dance with national and local codes Power Wiring The power supply lines must be run in weather tight conduit to the disconnect and into the bottom of the unit control box Provide strain relief for...

Page 16: ...ow 1 2 3 etc Connections should be made using 1 to 1 2 to 2 3 to 3 and so on See following example Zone Temperature Sensor Terminal Strip Terminal Terminal I D 1 ZTEMP 2 SIGNAL COMMON 3 CSP 4 MODE 5 H...

Page 17: ...17 Figure 11A Zone Sensor Interconnections...

Page 18: ...18 Figure 11B Conventional Thermostat Interconnections...

Page 19: ...plying unit After all electrical wiring is complete SET THE ZONE SEN SOR SWITCH TO THE OFF POSITION AND THE FAN SWITCH TO AUTO SO COMPRESSOR AND FAN WILL NOT RUN and apply power by closing the system...

Page 20: ...lock out Reset by disconnecting and re applying unit power Unit will start in the high fire mode After a short run cycle it will switch to low fire Note Blue smoke produced by the heat exchanger durin...

Page 21: ...this unit from the roof use the Test mode procedure on page 3 and 4 of this manual Operating Pressures After the unit has operated in the cooling mode for a short pe riod of time install pressure gaug...

Page 22: ...ons warrant Examine these areas of unit 1 Filters for cleaning or replacement 2 Motors and drive system components 3 Economizer gaskets for possible replacement 4 Condenser coils for cleaning 5 Safety...

Page 23: ...23...

Page 24: ...24...

Reviews: