![American Standard ACONT900AC43UA Installer'S Manual Download Page 8](http://html1.mh-extra.com/html/american-standard/acont900ac43ua/acont900ac43ua_installers-manual_2926015008.webp)
ACONT900AC43UA
Pub. No. 11-HD04D1-2
69-2080—05
8
Schedule Options
0160
4
0, 4
0 - Non-programmable
4 - 7 Day programmable
When ISU0160 is changed
from 0 (non-programmable
to 4 (programmable),
“Permanent Hold” will
display under the time icon.
This goes away when the
schedule key is hit or when
the schedule menu is
entered.
Restore Energy Star
Schedule
0165
0
0, 1
0 - No
1 - Resets the schedule to
default Energy Star
No ISU or USU settings
affected.
System Selection
0172
E
E, 1-3
E - Auto-Discover
1 - Heat/Cool
2 - Heat Pump
3 - Heat Only (no fan)
If no equipment is
connected during the Auto-
Discovery process, the
system mode will be stuck
at “off” and no equipment
will run.
Compressor Stages
0174
E
E, 0-2
E - Auto-Discover
0 - None
1 - Single Stage
2 - Two Stage/Two Step
A minimum of 1H or 1C is
required.
Heater Stages
0176
E
E, 0-3
E - Auto-Discover
0 - None
1 - Single Stage
2 - Two Stage
3 - Three stage
A minimum of 1H or 1C is
required.
Fan Operation
0180
E
E, 0, 1
E - Auto-Discover
0 - Equipment controls fan
operation in heat mode
(fossil).
1 - Comfort Control
controls fan operation in
heat mode (electric).
Only seen if ISU 0172 is set
to 1.
Indoor Unit Type
0181
E
E, 0, 1
E - Auto-Discover
0 - Non-variable Speed
1 - Variable Speed
Compressor Low
Stage Airflow
0182
E
2 Stage =
50%
2 Step =
80%
E, 25, 30,
35, 40,
45,
50, 55,
60,
65, 70,
75,
80
E - Auto-Discover,
25% - 80% in 5%
increments
Only shown for variable
speed indoor units.
Options may vary based on
actual system installed.
Compressor Stage 2
Airflow
0183
100%
100
Not Auto-discovered
Only shown for variable
speed indoor units.
Options may vary based on
actual system installed.
Heat Pump Warm Air
Discharge
0185
0
0, 1
0 - Disabled = 100%
1 - Enabled = 80%
Only shown for variable
speed indoor units.
Continuous Fan
Airflow
0186
50
25, 30,
35,
40, 45,
50,
55, 60,
65,
70, 75,
80,
85, 90,
95,
100
25% - 100% in 5%
increments
Only shown for variable
speed indoor units.
Table 4. Installer Setup Menu
Selection
Installer Setup
Number (ISU)
Factory
Setting
Choices
Comments
Option
Description