background image

© 2006 American Standard Inc.  All Rights Reserved

2

18-GE08D1-2

Installer’s Guide

B

A

JOIST

JOIST

JOISTS

HEADER

JOISTS

HEADER

NAILS

REAR

FLANGE

FRONT OF

UNIT

HEADER

1"

NAILS

HEADER

MIN. SPACING TO
ANY COMBUSTIBLE
MATERIAL.

1"

APPROX. 3/4" FLANGES ON FIELD
FABRICATED DUCT OR PLENUM

ONE INCH DUCT SPACERS

FLOOR

SUBBASE

UNIT

AIR HANDLER SUBBASE

6. If supplementary heat is to be added, power supply

must be sufficient to carry the load. In addition,
minimum air flow settings, unit and duct clearances
to combustible material must be maintained as stated
on the air handler rating nameplate.

CAUTION

!

For air handlers not equipped with a factory installed
electric heater, a field installed heater is available from
American Standard Inc. Only heaters built by American
Standard Inc. are approved for use in the air handler.
These heaters have been designed and tested in accor-
dance with UL standards to provide safe and reliable
operation. A list of approved heaters is provided on the
air handler rating nameplate.  Heaters that are not
factory approved could cause damage and are not
covered under equipment warranty.

NOTE:
If air handler is used WITHOUT a supplementary electric
heater, a sheetmetal plate is required to cover the open
hole in the airflow system. See Figure 2. Also seal the
cabinet air tight where the wire enters.

7. If field installed electric heaters are applied, mini-

mum air flow settings, unit and duct clearances to
combustibles must be maintained as stated on
the air handler rating nameplate.

8. If the unit is installed without a return air duct,

applicable local codes may limit this air handler to
installation only in a single story residence and
within conditioned space.

9. If the outdoor unit is to be installed later, or by

others, then installation of the air handler must be
made to allow access for refrigerant lines, or attach
refrigerant lines to air handler when installing.

10. Make sure there are provisions for installing

condensate drain lines.

This area may also be used for other purposes, includ-
ing an electric hot water heater – 

but in no case shall

a fossil fuel device be installed and/or operated in
the same closet, alcove or utility room.

In addition, these air handlers are suitable for installa-
tion in an attic, garage or crawl space with ducted
supply and return air.

This equipment has been evaluated in accordance with
the Code of Federal Regulations, Chapter XX, Part 3280
or the equivalent. “SUITABLE FOR MOBILE HOME
USE.”

For proper installation the following items must be
considered:

1. If adequate power is available and correct according to

nameplate specifications.

2. Insulate all ducts, particularly if unit is located

outside of the conditioned space.

3. To ensure maximum efficiency and system perfor-

mance, the existing supply and return duct system
static pressures must not exceed the total available
static pressure of the air handler.  Reference ACCA
Manual D, Manual S and Manual RS along with the
air handler Product Data and Service Facts for
additional information.

4. It is recommended that the outline drawing be studied

and dimensions properly noted and checked against
selected installation site. By noting in advance
which knockouts are to be used, proper clearance
allowances can be made for installation and possible
future service.

5. When air handler with supplementary heater is to

be installed in the downflow position on combus-
tible flooring an accessory subbase (TAYBASE101
for 2TEC3F18-36A, TAYBASE102 for 2TEC3F55
and TAYBASE100 for 2TEC3F42A-60A) must be
used. See Figure 1.

1

FLOOR OPENING - SIZE

 MODEL NO.

A

B

 TAYBASE100

23-3/4

14-13/16

 TAYBASE101

21-3/4

14-13/16

 TAYBASE102

26-3/4

14-13/16

Summary of Contents for 2/4TEC3F18A1000A

Page 1: ...instructions do not cover all variations in systems or provide for every possible contingency Should further information be desired or particular problems arise which are not covered sufficiently by...

Page 2: ...alled later or by others then installation of the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing 10 Make sure there are provi...

Page 3: ...liding the coil out on the coil channel supports The tray is detached by removing the two screws at the drain pan and the two screws holding the two brackets at the top of the coil b Remove the factor...

Page 4: ...e factory installed filter should then be removed from the unit b To convert the unit to horizontal left front access slide the coil out on the coil channel supports and rotate the complete coil 180 d...

Page 5: ...unit Evacuation leak testing and brazing procedures are included in those instructions Read those instruc tions before starting installation of refrigerant lines NOTE Torque specification for TXV equ...

Page 6: ...LD FABRICATEDTRAP 2 MIN 2 MIN CAP OR PLUG Trap must be within 4 of air handler condensate drain connection Close as possible 7 8 3 4 NPT Secondary drain connection 3 4 NPT Primary drain connection 6 9...

Page 7: ...ower NOTE If air handler is used with or without a heater the 7 8 electrical entry hole as well as any other cabinet penetrations must be sealed air tight HOOK UP DIAGRAMS G CONTROL WIRING 1 Connect w...

Page 8: ...GE08D1 2 Installer s Guide 2 4TEC AIR HANDLERS WITH SINGLE SPEED COOLING UNIT 1 STAGE HEAT 2 4TEC AIR HANDLER WITH SINGLE SPEED COOLING UNIT 2 STAGE HEAT From Dwg 21B801083 Rev 1 From Dwg 21B801081 R...

Page 9: ...5 5 77 3 62 1 89 TXV NB 5 8 1 4 1 2 1 4 TEC3F24A 3 4 5 16 5 8 5 16 TEC3F30A 45 17 57 3 4 5 16 TEC3F36A 7 8 3 8 3 4 3 8 TEC3F42A 51 75 23 50 21 50 18 33 4 65 6 77 3 4 3 8 TEC3F48A TEC3F60A 57 90 23 50...

Page 10: ...F24A 17 00 39 00 43 00 21 50 2 4TEC3F30A 19 00 41 00 45 00 21 50 2 4TEC3F36A 19 00 41 00 45 00 21 50 2 4TEC3F42A 23 80 47 75 51 75 23 50 2 4TEC3F48A 31 20 58 75 57 90 23 50 2 4TEC3F55A 29 00 53 90 57...

Page 11: ...s instruction on page 12 2 Operational Procedure for the system installation can be found in the outdoor unit installer guide and will be compatible with this Air Handler CAUTION Cardboard packing mat...

Page 12: ...STEM CHECKOUT PROCEDURES After installation has been completed it is recommended that the Air Handler be checked against the following checklist 1 Make sure power is OFF at power disconnect switch 2 C...

Reviews: