American Standard 2/4TEC3F18A1000A Installer'S Manual Download Page 4

4

18-GE08D1-2

Installer’s Guide

e. Pedestal and unit should be isolated from the

foundation using a suitable isolating material.

DOWNFLOW

a.

For maximum efficiency

, the horizontal drip

tray should be removed. Tray removal requires
that the coil be removed by sliding the coil out on
the coil channel supports. The tray is detached
by removing the two screws at the drain pan
and the two screws holding the two brackets at
the top of the coil.

b. Remove the factory installed baffle assembly

from the apex of the coil by removing the 5/16"
hex head screws.

Replace this baffle with the factory supplied
narrow coil baffle using the screws removed
previously (See Figure 3).

NOTE:
INSTALLATION OF THE DOWNFLOW BAFFLE KIT
INCLUDED WITH UNIT IS REQUIRED ON
DOWNFLOW APPLICATIONS. SEE FIGURE 4.

c. Detach the coil from the drain pan by removing

4 screws as shown in Figure 4.

d. Remove the front triangular baffle from the coil and

install the 1/2" wide gasket provided per Figure 4.
Trim the gasket length to fit the baffle. Reinstall
the baffle to coil, with gasket material compressed
against the coil.

e. Install the water blow-off baffles provided on each

side of the coil with the flange at the top as shown
in Figure 4. The bottom of the baffle is to be as
close to the bottom of the coil as possible.

f. Install the 7/8" wide gasket in each side of the

drain pan as shown in Figure 4 (sect. X-X).

g. Place the 2 water diverter baffles (

5 ton model

only

) underneath the coil on the inside edge of

the drain pan, Figure 4. Fill the bend in the
baffle which fits the inner edge of the drain pan
with RTV type adhesive/sealant before install-
ing the baffle.

h. The unit is then placed with the blower side

down and the coil is replaced on the coil channel
supports with the drain connections at the
bottom. The unit is now in downflow position
with front access.

i. When air handler with supplementary heater is

to be installed in the downflow position on
combustible flooring an accessory subbase
(TAYBASE101 for 2TEC3F18A-36A,TAYBASE101
for 2TEC3F18A and TAYBASE100 for
2TEC3F42A-60A) must be used.  See Figure 1.

HORIZONTAL LEFT

 a.

For maximum efficiency

 and Customer ease of

filter maintenance, it is recommended that a
properly sized 

remote filter 

and grille be installed

for horizontal applications. Airflow should not
exceed the face velocity of the filter being used. 

The

factory installed filter should then be
removed from the unit

.

b. To convert the unit to horizontal left, front access,

slide the coil out on the coil channel supports and
rotate the complete coil 180 degrees.

c. Remove the factory installed baffle assembly

from the apex of the coil by removing the 5/16"
hex head screws. Replace this baffle with the
factory supplied narrow coil baffle using the
screws removed previously (See Figure 3).

d. The coil is then inserted back into the cabinet on

the opposite side coil channel supports. The unit is
now horizontal left with front access.

e.

Openings where field wiring enters the
cabinet must be completely sealed.

 Location of

power entry is shown on the Outline Drawing.

f.

Cage nuts are not provided for horizontal
left suspension.

 However, if the unit is sus-

pended, it

must be supported from the

bottom near both ends as well as the middle to
prevent sagging. The service access must remain
unobstructed.

If the unit is not suspended it must be supported
as mentioned above and isolated carefully to
prevent  sound transmission. Vibration isolators
(purchased locally) must be placed under the unit.

g. It is always recommended that an auxiliary drain

pan be installed under a horizontal air handler (See
Condensate Piping) to prevent possible damage to
ceilings.

h. Isolate the auxiliary drain pan from the unit or

from the structure.

i. Connect the auxiliary drain pan to a separate

drain line (no trap is needed in this line) or route
outside the structure to a conspicuous location in
accordance with national and local codes.

HORIZONTAL RIGHT

a.

For maximum efficiency

 and Customer ease of

filter maintenance, it is recommended that a
properly sized 

remote filter 

grille be installed for

horizontal applications. Airflow should not exceed
the face velocity of the filter being used. 

The

factory installed filter should then be re-
moved from the unit.

b. Unit is shipped from the factory in the upflow or

horizontal right configuration. Unit conversion is
not required.

c. The air handler is designed to be suspended by

using the cage nuts provided in the unit.  Six 1/4"
– 20 threaded rods are required for the
2TEC3F18-42A models and Eight threaded rods
are required for the 2TEC3F48-60A models.
Other means of suspension are allowed as long
as the unit is supported from both ends as well as
the middle to prevent sagging and service access
is not obstructed.

d. If the unit is not suspended it must be isolated

carefully to prevent sound transmission. Vibration
isolators (purchased locally) must be placed
under the unit.

Summary of Contents for 2/4TEC3F18A1000A

Page 1: ...instructions do not cover all variations in systems or provide for every possible contingency Should further information be desired or particular problems arise which are not covered sufficiently by...

Page 2: ...alled later or by others then installation of the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing 10 Make sure there are provi...

Page 3: ...liding the coil out on the coil channel supports The tray is detached by removing the two screws at the drain pan and the two screws holding the two brackets at the top of the coil b Remove the factor...

Page 4: ...e factory installed filter should then be removed from the unit b To convert the unit to horizontal left front access slide the coil out on the coil channel supports and rotate the complete coil 180 d...

Page 5: ...unit Evacuation leak testing and brazing procedures are included in those instructions Read those instruc tions before starting installation of refrigerant lines NOTE Torque specification for TXV equ...

Page 6: ...LD FABRICATEDTRAP 2 MIN 2 MIN CAP OR PLUG Trap must be within 4 of air handler condensate drain connection Close as possible 7 8 3 4 NPT Secondary drain connection 3 4 NPT Primary drain connection 6 9...

Page 7: ...ower NOTE If air handler is used with or without a heater the 7 8 electrical entry hole as well as any other cabinet penetrations must be sealed air tight HOOK UP DIAGRAMS G CONTROL WIRING 1 Connect w...

Page 8: ...GE08D1 2 Installer s Guide 2 4TEC AIR HANDLERS WITH SINGLE SPEED COOLING UNIT 1 STAGE HEAT 2 4TEC AIR HANDLER WITH SINGLE SPEED COOLING UNIT 2 STAGE HEAT From Dwg 21B801083 Rev 1 From Dwg 21B801081 R...

Page 9: ...5 5 77 3 62 1 89 TXV NB 5 8 1 4 1 2 1 4 TEC3F24A 3 4 5 16 5 8 5 16 TEC3F30A 45 17 57 3 4 5 16 TEC3F36A 7 8 3 8 3 4 3 8 TEC3F42A 51 75 23 50 21 50 18 33 4 65 6 77 3 4 3 8 TEC3F48A TEC3F60A 57 90 23 50...

Page 10: ...F24A 17 00 39 00 43 00 21 50 2 4TEC3F30A 19 00 41 00 45 00 21 50 2 4TEC3F36A 19 00 41 00 45 00 21 50 2 4TEC3F42A 23 80 47 75 51 75 23 50 2 4TEC3F48A 31 20 58 75 57 90 23 50 2 4TEC3F55A 29 00 53 90 57...

Page 11: ...s instruction on page 12 2 Operational Procedure for the system installation can be found in the outdoor unit installer guide and will be compatible with this Air Handler CAUTION Cardboard packing mat...

Page 12: ...STEM CHECKOUT PROCEDURES After installation has been completed it is recommended that the Air Handler be checked against the following checklist 1 Make sure power is OFF at power disconnect switch 2 C...

Reviews: