![American Standard 2/4TEC3F18A1000A Installer'S Manual Download Page 3](http://html1.mh-extra.com/html/american-standard/2-4tec3f18a1000a/2-4tec3f18a1000a_installers-manual_2925456003.webp)
18-GE08D1-2
3
Installer’s Guide
11. If side, front or rear return is required, air handler
must be elevated or placed on a plenum
(TAYPLNM100). Connecting return duct directly to
the side, front or rear of the cabinet is not ap-
proved.
12. Route refrigerant and condensate drain lines away
from air handler so they do not interfere with
access panels and filters.
13. When external accessories are used, the additional
height and width requirements must be considered
in the overall space needed.
14. These units are not approved for outdoor installa-
tion.
15. These units are approved for draw-through
application only
NOTE: Condensation may occur on the
surface of the air handler when installed in an
unconditioned location.When units are in-
stalled in unconditioned spaces, verify that all
electrical and refrigerant line penetrations on
the air handler are sealed completely.
NOTE: When installing the 4 and 5 ton air
handlers in attic or tight applications, the
cabinet may be disassembled into two sec-
tions.
B. UNIT INSTALLATION
UPFLOW
a.
For maximum efficiency
, the horizontal drip
tray should be removed. Tray removal requires
that the coil be removed by sliding the coil out
on the coil channel supports. The tray is
detached by removing the two screws at the
drain pan and the two screws holding the two
brackets at the top of the coil.
b. Remove the factory installed baffle assembly
from the apex of the coil by removing the 5/16"
hex head screws.
Replace this baffle with the factory supplied
narrow coil baffle using the screws removed
previously (See Figure 3).
c. Position unit on Pedestal or other suitable
foundation. If Pedestal is not used, a frame
strong enough to support the total weight must
be provided.
Provide a minimum height of 14 inches for
proper unrestricted airflow.
d. If a return air duct is connected to the air han-
dler, it must be the same dimensions as shown in
the outline drawing.
From Dwg. 21B140413
4"
6"
17"
1"
3/8"
1/4" HOLES (4)
ACCESSORY BAY99X123
IF AIRHANDLER IS USED
WITHOUT
A FACTORY FURNISHED
SUPPLEMENTARY HEATER, A PLATE IS REQUIRED TO COVER
THE OPEN HOLE IN THE AIR FLOW SYSTEM
DOWNFLOW BAFFLE KIT
X
X
7/8" GASKET
SCREWS TO
REMOVE COIL
SCREWS TO
REMOVE COIL
DISCARD HORIZONTAL
DRIP TRAY
1/2" GASKET
INSIDE SURFACE
OF BAFFLE
7/8" GASKET
SECT. X-X
(TYP. BOTH SIDES)
FILL WITH SEALANT
WATER
BLOW-OFF
BAFFLES
ATTACH WITH
2 SCREWS
EACH SIDE
WATER
DIVERTER
BAFFLES
(5TON ONLY)
2
4
Remove
and
Discard
Replace
with
Narrow
Baffle
FOR MAXIMUM EFFICIENCY ON
HORIZONTAL LEFT,
UPFLOW AND DOWNFLOW
3