Sprinkler Option Temperature Controller Settings
NOTE:
Refer to Controllers Users Manual for further information on controller options.
Message
Display
Message
Description
Settings
SP
TEMPERATURE
SET POINT
575º F OR 301.6º C
ALHi
ALARM HI
575º F OR 301.6º C
(NOTE: ADJUST SAME AS SP)
InP
INPUT DEVICE
P 385 = RTD
INPUT
F-C
º F OR º C
SELECT TYPE REQUIRED
(FAHRENHEIT OR CELSIUS)
dpt
DECIMAL POINT
0,
N
O DECIMAL POINT
InPt
INPUT FAULT TIMER
0.2
SPL
SET POINT LOW
500
(SETTING CAN NOT BE LOWER)
SPH
SET POINT HIGH
700
(SETTING CAN NOT BE HIGHER)
SPSt
SET POINT STATE
rE
(REVERSE ACTION)
SPOL
SET POINT OUTPUT
LOW LIMIT
0%
(NOT USED)
SPOH
SET POINT OUTPUT
HIGH LIMIT
100%
(NOT USED)
SPLP
SET POINT LAMP
0 OFF
(LAMP OFF WHEN OUTPUT IS ON)
AL
HIGH ALARM ONLY
Hi
ALt
ALARM TYPE
Abs
(ABSOLUTE ALARM)
ALrE
ALARM RESET
OnOf
(AUTOMATIC RESET)
ALPi
ALARM POWER
INTERRUPT
OFF
(ALARM INHIBIT IS OFF)
ALiH
ALARM INHIBIT
OFF
(ALARM INHIBIT IS OFF)
ALSt
ALARM OUTPUT
STATE
CLOS
(CLOSES CONTACTS AT ALARM SET POINT)
ALLp
ALARM LAMP
O ON
(ALARM LAMP IS ON WHEN ALARM
CONTACT IS CLOSED)
SECr
SECURITY CODE
FULL SECURITY -
SET TO 110 (DISPLAYED AS 1) "VIEW ONLY"
NO SECURITY -
SET TO 111 (DISPLAYED AS 4)
"ALL FEATURES UNLOCKED"