28
American Dryer Corp.
113354 - 20
Shaded areas are stated in metric equivalent
* Drill Measurement Size (D.M.S.) equivalents are as follows:
** Check dryers rating plate.
Natural Gas .............................. #1 = 0.2280” (5.7912 mm).
#6 = 0.2040” (5.1816 mm) for 190 (AGA)
..................................................
#13 = 0.1850” (4.699 mm) for 190DR.
L.P. Gas .................................... #28 = 0.1405” (3.5687 mm).
#31 = 0.1200 (3.048 mm) for 190 (AGA).
..................................................
#33 = 0.1130” (2.870 mm) for 190DR.
2. Technical Data
a. Gas Specifications
TYPE OF GAS
NATURAL
LIQUID PROPANE
Manifold Pressure*
3.5 inches W.C.
8.7 mb
10.5 inches W.C.
26.1 mb
In-Line Pressure
6.0 - 12.0 inches W.C.
14.92 - 29.9 mb
11.0 inches W.C.
27.4 mb
TYPE OF GAS
Liquid
Propane
Conversion Kit
Part Number
Btu/hr
**
Rating
kcal/hr
Rating
Natural
Liquid Propane
Qty.
D.M.S.
*
Part No. Qty.
D.M.S.
*
Part No.
590,000
148,680
4
#1
140840
4
#28
140821
882222
470,000
118,517
4
#6
140833
4
#31
140818
887249
404,000
101,874
4
#13
140860
4
#33
140855
882252
Shaded areas are stated in metric equivalents
* Measured at the gas valve pressure tap when the gas valve is on.
b. Gas Connections:
Inlet connection -------------- 1-1/2” N.P.T.
Inlet supply size -------------- 1-1/2” Pipe (minimum)
Btu/hr input (per dryer) ---- 590,000 (148,680 kcal/hr)
----------------------------------
470,000 (118,517 kcal/hr) for MLG-190 (AGA)
----------------------------------
404,000 (101,874 kcal/hr) for MLG-190DR
1) Natural Gas
Regulation is controlled by the dryer’s gas valve’s internal regulator. Incoming supply pressure
must be
consistent between a minimum of 6.0 inches (14.92 mb) and a maximum of 12.0 inches
(29.9 mb) water column (W.C.) pressure.
2) Liquid Propane (L.P.) Gas
Dryers made for use with L.P. gas have the gas valve’s internal pressure regulator blocked open so
that the gas pressure
must be
regulated upstream of the dryer. The pressure measured at each
gas valve pressure tap
must be
a consistent 10.5 inches (26.1 mb) water column. There is no
regulator or regulation provided in an L.P. dryer. The water column pressure
must be
regulated at
the source (L.P. tank) or an external regulator
must be
added to each dryer.