73
4. RTD (Resistive Temperature Device) WIRING TO THE EXHAUST 4 to 20 MILLIAMPERE
(4 to 20 mA) TRANSMITTER
Check
ALL
wiring and ADS-464 connection from the exhaust RTD (Resistive Temperature Device) probe
to the exhaust 4 to 20 milliampere (4 to 20 mA) transmitter. Refer to the ADS-464 EXHAUST Temperature
Assembly and Wiring Diagram, ADS-464 Main Panel Wiring Diagram.
5. CIRCUIT WIRING TO THE ANALOG INPUT MODULE
Check
ALL
wiring and connections from the 4 to 20 milliampere (4 to 20 mA) transmitter to the PLC
(Programmable Logic Controller) Analog Input Module. Refer to the ADS-464 Main Panel Wiring Diagram.
F. MOTORS
INTRODUCTION
The four (4) motors installed on the ADS-464 are connected directly to associated thermal magnetic starters in
the main electrical enclosure. The troubleshooting information included in this section will cover the actuation,
power control and safety devices to these motors.
The ADS-464 motors include:
MAIN BLOWER FAN MOTOR
BURNER FAN MOTOR
LEFT TUMBLER (BASKET) MOTOR
RIGHT TUMBLER (BASKET) MOTOR
Refer to the following diagrams for functional and wiring information:
ADS-464 MAIN PANEL WIRING DIAGRAM
ADS-464 SYSTEM BLOCK DIAGRAM
Motor Actuating Device Information
ALL
ADS-464 motor contactors have 110 volt 50/60 Hz actuation coils. Three (3) motor contactors are
actuated by outputs from the PLC (Programmable Logic Controller), and one contactor is actuated by
the Burner Controller Module (BCM).
Motor Protection Device Descriptions
The motor protection devices in the ADS-464 incorporate a manual disconnect switch, thermal overload
relay, and instantaneous trip mechanism in one compact device. A two (2) position, normally open,
auxiliary contact block has been attached to
ALL
motor protection devices to provide the MOTOR
FAULT display message, and shut down
ALL
motors in the event a motor should trip.
1. MOTOR ACTUATION PROBLEMS
a.
PROBABLE CAUSES;
1) Motor Protection Device OFF or TRIPPED.
Summary of Contents for ADS-464 II
Page 80: ...ADC113074 1 01 24 00 10 ...