2. Electrical Service Specifications
IMPORTANT:
The dryer
must be
connected to the electric supply shown on the data label that is
affixed to the right side of the main electrical enclosure. In the case of 208 VAC or
240 VAC, the supply voltage
must match
the electric service specifications of the
data label
exactly
.
WARNING: 208 VAC and 240 VAC ARE NOT THE SAME.
Any damage done to the dryer
components due to improper voltage will automatically VOID THE WARRANTY.
IMPORTANT:
For proper sprinkler and dryer operation, sprinkler
must be
powered by a separate
or dedicated single-phase (1ø) multi-wire branch circuit at dryers nameplate voltage.
NOTE:
For 4-wire service, cap the neutral.
NOTE:
Contact the factory for electrical information not listed.
NOTE: ADC
reserves the right to make changes in specifications at any time, without notice or
obligation.
ADS-464 (Steam)
E
LECTRICAL
S
ERVICE
S
PECIFICATIONS
(
PER DRYER
)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES:
A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct
breaker size according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3Ø dryer must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz
50 Hz
208
3ø
3/4
112
112
1/0
150
150
240
3ø
3/4
107
108
1
150
1
50
380
3ø
3/4
---
63
4
100
100
416
3ø
3/4
---
60
4
90
100
460
3ø
3/4
53
---
4
80
90
D
EDICATED
S
PRINKLER
S
ERVICE
Dryer Nameplate
1ø
---
2
16
3.5
5
* AWG Stranded Type Wire ... for individual lengths less than 100 feet (31 m).