SMD34K User Manual
ADVANCED MICRO CONTROLS INC.
96
3.2 Create New PLC Task
You only have to follow this step if the Main PLC task timing verified in step 3.1 above is not the correct
update time for the SMD34K and the correct time is not an integer multiple of the Main PLC task timing.
1) In the
Solutions Explorer
, expand out
System
Tasks
so that the tasks are visible. Right click on
Tasks
and
select “Add New Item...”.
2) In the window that opens, name the new task and select “TwinCAT Task With Image” as the
Type
. Click
the [OK] button to accept the values.
Figure T3.2 Create New Task
3) In the window that open, enter the desired update time in Cycle Ticks. By default, each Cycle Tick is 1
millisecond.
4) If needed, expand out the new task so that the Outputs icon is visible.
5) Right click on the Outputs icon and select “Add New Item...”. The
Insert Variable
window will open.
6) Name the new variable. Under
>Data Type
, select “UINT”. Click the [OK] button to close the
Insert
Variable
window.
Figure R6.6 Setting Task Variable Name and Size
Summary of Contents for SMD34K
Page 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S280 ...
Page 6: ...TABLE OF CONTENTS SMD34K User Manual ADVANCED MICRO CONTROLS INC 6 Notes ...
Page 50: ...CALCULATING MOVE PROFILES SMD34K User Manual ADVANCED MICRO CONTROLS INC 50 Notes ...
Page 62: ...CONFIGURATION DATA FORMAT SMD34K User Manual ADVANCED MICRO CONTROLS INC 62 Notes ...
Page 80: ...COMMAND DATA FORMAT SMD34K User Manual ADVANCED MICRO CONTROLS INC 80 Notes ...
Page 100: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC ...