NXEE2 Programmable Parameters (continued)
Channel Setup Parameters (continued)
Network Input Data Format
The following values can be transmitted to the host controller in the Network Input Data:
Data Value
Velocity
Captured Data Value
Actual SSI Data
There are only five data words available to each channel. Therefore the NXEE2 can only transmit two values
at a time. The Network Input Data Format parameter allows you to choose which values are transmitted.
The NXEE2 can take up to four milliseconds to accept a change in format and begin transmit-
ting the newly selected values. If your network interface updates the Network Input Data at a
rate faster than four milliseconds, it may take multiple reads before the change in selected val-
ues is seen.
Programming Cycle
New parameter values are written to the NXEE2 through a Programming Cycle. A Programming Cycle con-
sists of six steps and is controlled by the Transmit Bit in the Network Output Data and the Acknowledge Bit
in the Network Input Data.
1) Write the new programming data into the registers assigned to the module with the Transmit Bit
reset. This step insures that the correct data is in the registers before the Programming Cycle begins.
2) Set the Transmit bit. A Programming Cycle is initiated when this bit makes a 0
1 transition.
3) Once the NXEE2 is done with the programming data, it will set any necessary error bits and the
Acknowledge Bit in the Network Input Data.
4) Once you see the Acknowledge Bit set, check for any errors. The error bits are guaranteed valid
while the Acknowledge Bit is set.
5) Respond to any errors and reset the Transmit Bit.
6) The NXEE2 responds by resetting the Acknowledge Bit. The Programming Cycle is now complete.
All parameters are checked before any of them are applied. If there is an error in the block of
data, the NXEE2 will only set the appropriate error bits in the Network Input Data. Parameters
are not applied to the NXEE2 until all of the data is correct.
Summary of Contents for NXEE2
Page 22: ...DATA FORMATS NXEE2 User Manual ADVANCED MICRO CONTROLS INC 22 Notes ...
Page 32: ...INSTALLING THE NXEE2 NXEE2 User Manual ADVANCED MICRO CONTROLS INC 32 Notes ...
Page 40: ...SET THE IP ADDRESS AND PROTOCOL NXEE2 User Manual ADVANCED MICRO CONTROLS INC 40 Notes ...
Page 42: ...PROTOCOL SPECIFIC INFORMATION NXEE2 User Manual ADVANCED MICRO CONTROLS INC 42 Notes ...
Page 54: ...IMPLICIT COMMUNICATIONS WITHOUT EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 54 Notes ...
Page 60: ...ETHERNET IP EXPLICIT MESSAGING EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 60 Notes ...
Page 64: ...MODBUS TCP CONFIGURATION Modbus TCP Protocol ADVANCED MICRO CONTROLS INC 64 Notes ...
Page 72: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC ...
Page 74: ...PROFINET NETWORK CONFIGURATION PROFINET Protocol ADVANCED MICRO CONTROLS INC 74 ...