![AMCI NXEE2 User Manual Download Page 63](http://html.mh-extra.com/html/amci/nxee2/nxee2_user-manual_2921185063.webp)
20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254 Fax: (860) 584-1973 http://www.amci.com
Modbus TCP Protocol
M
ODBUS
TCP C
ONFIGURATION
63
Supported Modbus Functions
Table T6.1 Supported Modbus Functions
Table T6.1 above lists all of the Modbus functions supported by an NXEE2. AMCI supports all of these func-
tions so that you can control the unit as you see fit. However, if you are looking for the easiest way to inter-
face with your unit, then you only need to use the
Read/Write Registers
function, which is function code 23.
Each NXEE2 buffers the data that is sent to it over the network. If you use the
Read/Write Reg-
isters
function to write data to the unit, the data read with that command will not contain the
response to the new write data. The response to the new data will be sent with the next data
read.
Supported Modbus Exceptions
Table T6.2 Supported Modbus Exceptions
Function
Code
Function Name
NXEE2
Register
Addressing method
1
Read Coils
OUTPUT
Bit:Addresses starting at 16,384
2
Read Discrete Inputs
INPUT
Bit:Addresses starting at 0
3
Read Holding Registers
OUTPUT & INPUT
Word: Out Regs.Starting at 1024
In Regs.Starting at 0
4
Read Input Registers
INPUT
Word:Addresses starting at 0.
5
Write Single Coil
OUTPUT
Bit:Addresses starting at 16,384
6
Write Single Register
OUTPUT
Word:Addresses starting at 1024
15
Write Multiple Coils
OUTPUT
Bit:Addresses starting at 16,384
16
Write Multiple Registers
OUTPUT
Word:Addresses starting at 1024
22
Mask Write Register
OUTPUT
Word:Addresses starting at 1024
23
Read/Write Registers
INPUT/OUTPUT
Word: Out Regs.Starting at 1024
In Regs.Starting at 0
Code
Name
Description
01
Illegal function
The NXEE2 does not support the function code in the query.
02
Illegal data address
The data address received in the query is outside the initialized memory area.
03
Illegal data value
The data in the request is illegal.
Summary of Contents for NXEE2
Page 22: ...DATA FORMATS NXEE2 User Manual ADVANCED MICRO CONTROLS INC 22 Notes ...
Page 32: ...INSTALLING THE NXEE2 NXEE2 User Manual ADVANCED MICRO CONTROLS INC 32 Notes ...
Page 40: ...SET THE IP ADDRESS AND PROTOCOL NXEE2 User Manual ADVANCED MICRO CONTROLS INC 40 Notes ...
Page 42: ...PROTOCOL SPECIFIC INFORMATION NXEE2 User Manual ADVANCED MICRO CONTROLS INC 42 Notes ...
Page 54: ...IMPLICIT COMMUNICATIONS WITHOUT EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 54 Notes ...
Page 60: ...ETHERNET IP EXPLICIT MESSAGING EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 60 Notes ...
Page 64: ...MODBUS TCP CONFIGURATION Modbus TCP Protocol ADVANCED MICRO CONTROLS INC 64 Notes ...
Page 72: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC ...
Page 74: ...PROFINET NETWORK CONFIGURATION PROFINET Protocol ADVANCED MICRO CONTROLS INC 74 ...