2600-13 Press Control Module
MicroLogix 1500 & CompactLogix Resolver Module
Revision 2.1
Configuring a MicroLogix 1500 PLC for the 2600-13 module
1.
Open or create the RSLogix 500 project in which you want to use the 2600-13 module.
2.
Double click on I/O Configuration in the project tree.
3.
Select the slot where the 2600-13 module will be installed.
4.
Double click on “Other.. Requires I/O Card Type ID” from the bottom of the list of available
modules.
5.
Enter the following information in the window that appears.
Vendor ID:
3
Product Type:
9
Product Code:
27
Input Words:
8
Output Words:
8
Input Bits:
0
Output Bits:
0
Extra Data Length:
0
Ignore Configuration Error:
Your Choice, but not recommended
6.
The 2600-13 module will now appear in the I/O Configuration with a Part Number of Other and a
Description of I/O Module – ID Code = 27.
7.
Input Data (data from the 2600-13 module to the PLC) will appear in Input Image Table registers
I:X.0 to I:X.7, where X is the slot number.
Output Data (data from the PLC to the 2600-13 module) will be written to registers O:X.0 to
O:X.7, where X is the slot number.
Because of a problem with the communication ASIC, it may necessary to use the
following rungs to increase the scan time of your ladder logic program.
The value that you use in register N7:1 may be different.