2600-13 Press Control Module
MicroLogix 1500 & CompactLogix Resolver Module
Revision 2.1
Timed Outputs
All 32 of the 2600-13 modules outputs can be programmed as Timed Outputs. There are two types of Timed
Outputs, Time or Position or Absolute Time.
Both types have a range of 1 to 32767ms.
When programmed for
Time or Position
, the output will turn on at the programmed Setpoint and turn off
either at the other Setpoint or at the Programmed Time value, whichever occurs first.
When programmed for
Absolute Time
, the output will turn on when either edge of the FROM TO window is
reached, and turn off at the programmed time value. The setpoint at the other edge of the programmed
window is not used.
From Setpoint To Setpoint
Programmed Setpoints
Output
Programmed Time Value
From Setpoint To Setpoint
Programmed Setpoints
Output
Programmed Time Value
Setpoint reached before Time value
Time value reached before setpoint
From Setpoint To Setpoint
Programmed Setpoints
Output
Programmed Time Value
From Setpoint To Setpoint
Programmed Setpoints
Output
Programmed Time Value
To setpoint less than the Time value
Time value less than the TO setpoint
If an input is being used as an ANDing condition to a Timed Output, the timer
will only start timing after the input has transitioned from Inactive to Active.
If Simple ANDing is being used, the timing function will be reset each time the
input transitions from Inactive to Active.
If Pulsed or Window ANDing is used, the timing function will reset itself only
when the resolver position has reached the next enable window.