36
8.1
To Start the Heater
1. First ensure that the gas supply to each
heater is turned on by opening the main
gas shut off valve.
2. Ensure that the setting of any time switch
and thermostat are such that the heating
system will be required to operate.
3. Switch o the electricity supply to the
heater. The fan will start, the ‘power on’
light on the burner will illuminate and
ignition commence.
4. Ignition will occur.
5. If ignition is successful the gas valve will
close and the spark ignition de-energize
after approximately 10 seconds. For
approximately 10 - 20 seconds the fan will
purge the system then re-ignition will be
attempted. After 3 attempts at ignition the
control unit will ‘lock-out’, the ‘power on’
lamp will remain illuminated and the fan will
continue to run. To reset after ‘lockout’,
switch off the power supply to the heater
and wait 5 minutes. Then turn the power on.
If repeated ‘lockout’ occurs investigate the
cause.
8.2. To Switch Off Heater
1. Switch off electrical supply to the heater.
The burner will stop and the fan will shut off.
8.3. Servicing
1. To ensure continued efficient and safe
operation it is recommended that the heater
be serviced regularly by a qualified person
every year in normal working conditions but
in exceptionally dusty or polluted conditions
more frequent servicing may be needed.
8. User & Operating Instructions.
Document re
feren
ce number
US/V
S/1
9/0710
AmbiRad is the manufacturer of a series of tubular infra-red heaters designed for overhead heating
of industrial and commercial buildings. Individual heating units are suspended from the roof or
mounted at an angle on the wall
1.
This appliance must only be installed by qualified craftsmen in accordance with
the requirements of local and National Codes.
2.
This appliance must be grounded in accordance with the National Electrical
Code ANSI/NFPA No.70.
3.
Never rest anything, especially ladders against the heaters.
Ambi-Rad Limited P.O. Box 617
Fishers, Indiana 46038
Telephone 317-577-0337
Facsimile 317-842-3989
Website
www.ambirad.com/us
For the Distributor Nearest please call
1-888-330-4878
AmbiRad is a registered trademark of AmbiRad Limited. Because of continuous product
innovation, AmbiRad reserves the right to change product specification without due notice.
Your Local Representative