Ambirad HCHE 120 Installation Servicing & Operating Instructions Download Page 23

 

 23/30 

Table 14 

VCHE 
HCHE 

Working point 

Rt 25°C 

Switching 

point 

30 
40 
50 
60/75 
90 
120 
140 
150/180 
215 
250 

!

52°C 

!

55°C 

!

40°C 

!

51°C 

!

77°C 

!

84°C 

!

50°C 

!

53°C 

!

52°C 

!

60°C 

100°C 
100°C 

90°C 
90°C 

100°C 
100°C 

90°C 
90°C 
90°C 
90°C 

 

5.2 Commissioning 

Procedure 

5.2.1 

Do not proceed with this section unless all 

parts of section 6.1.2 have been 
successfully completed.  In the event that 
one part does not comply DO NOT 
PROCEED.  Seek assistance from the 
supplier.  Refer to the burner manual, 
supplied separately, ensuring all setting 
data is known before commencing. 
(a)  Turn on electrical supply and adjust 

panel to ‘heat’ mode. 

(b)  Check that burner goes through 

correct ignition sequence and goes to 
’lock-out’. 

(c)  Adjust panel to ‘off’ mode.  If the 

burner does not go to lockout DO 
NOT PROCEED until the fault has 
been correctly identified and 
repaired.  

(d)  Switch on the gas supply and 

connect a suitable manometer to the 
test point on the burner prior to the 
combustion head. 

 

(e)  Adjust panel to ‘heat’ mode and reset 

the control box from lockout. The 
burner will start and a head gas 
pressure will be indicated on the 
manometer.  Check this value is in 
line with the technical specification in 
section 2.  If not adjust governor on 
gas valve accordingly. See burner 
manual accompanying this manual. 

(f)  Using approved and calibrated 

combustion analysis equipment to 
measure the percentage CO

2

. CO, 

gross flue temperature and ambient 
temperature. 

(g) If 

the 

CO

2

 levels do not correspond 

to the technical specification in 
section 2 adjust the primary air 
damper, more open for less CO

2

 and 

more closed for more CO

2

, until the 

correct level has been obtained. 
The CO2 level on the site must be 
lower than 10% & higher than 8.5%. 

(h)  Re-check all readings and enter on 

the commissioning sheet. 

(i)  From readings calculate the net 

efficiency of the unit.  This is not to 
be less than 84%. 

(j) 

The operation of the fan/limit stat is 
checked as follows : 

*for types 30-75

 (direct driven 

blowers) : by depressing and holding 
the main fan starter overload button. 

*for types 90-250

 (V-belt driven) : by 

removing the red wire of the fan stat. 

 

This will stop the main fan without 
stopping the burner.  After 3 minutes 
the burner will stop. 

(k) 

If the burner has not stopped release the 
button and allow the main fan to cool 
down the heater.  Then check the 
following:- 

 

-    Fan & limit stat settings are correct. 

The bi-metal strip has not been  

 damaged. 

 

The bi-metal strip casing is not in  

 

contact with the heat exchanger  

 body. 

(l) 

Adjust temperatures and time periods to 
ensure that the burner operates when 
required by the controls. 

(m)  Adjust panel to ‘off’ mode’.  The burner 

will stop.  Note the time it takes for the 
fan to stop, approximately two minutes, 
thus ensuring the fan side of the fan/limit 
stat is operating correctly. 

(n)  Complete the commissioning sheet and 

return a copy to the Service Department. 

 
In the event of any problems occurring during 
the commissioning process, which cannot be 
properly, rectified please consult the Technical 
Department of Ambi-Rad Limited. 

 

5.3 Commissioning 

Outlets 

For free standing heaters it is essential to 
ensure that the nozzled outlet louvres 
(discharge or plenum louvres) have been 
adjusted to the required angle of discharge 
and have been rotated to give the optimum 
distribution of air throughout the premises. 
Take care to avoid the short cutting of hot air 
back into the fan system, i.e. when installed 
close to a wall, as this can lead to a nuisance 
overheating condition. 
Securely fix all nozzle outlets after final 
adjustments have been made. 
Outlets for ducted systems are generally 
adjusted by the ductwork-commissioning 
engineer.  On completion ensure that the 
static pressure at the top of the heater does 
not exceed that as quoted in the technical  
specification in section 2 of this manual   This 
can be achieved by the use of a manometer 
taking a pressure reading in the plenum of the 
ductwork.  Also check the running current of 
the main fan motor. 
If the ductwork pressure is correct then the 
running current will be as quoted on the data 
plate.  If the static pressure is too low this will 
be verified by a high running current, which 
could lead to premature failure of the fan 
motor. Consequently, the ductwork outlet 
grilles will have to be closed to increase the 
static pressure. If the static pressure is too 
high this will be verified by a low running 
current of the motor, which could lead to 
overheating of the heater. The limiter will trip 
out.  Consequently the duct grilles will have to 
be opened. 

 

5.4 User 

Instructions 

(a)  Complete all commissioning data on the 

commissioning sheet. 

(b)  Instruct end user in correct operation and 

function of heater and ancillary controls.  
Particular awareness should be made to 
start up and shut down of the equipment. 

Summary of Contents for HCHE 120

Page 1: ...Leave it with the user or attached to the appliance or gas service meter after installation WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury...

Page 2: ...ectrical Connection 3 3 Ventilation Requirement 4 0 Installation 4 1 Location 4 2 Heater Clearances 4 3 Flue 4 4 Nozzled Heaters 4 5 Ducted Heaters 4 6 Filters 4 7 Controls 5 0 Commissioning 5 1 Pre C...

Page 3: ...ered gas installers 1 1 7 Warning Unauthorised modification of this appliance or departure from use in the manner for which it was intended by the manufacturer or installation in a manner contrary to...

Page 4: ...cations Each heater must have its own individual open flue 1 4 2 All cabinet heaters are fitted with a pre tested and set forced draught burner A sequential control box is fitted to each burner to pro...

Page 5: ...0 GS20 GS20 GS20 Minimum gas inlet mbar 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 17 5 20 pressure ins WG 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8...

Page 6: ...0 39 39 41 45 42 heater nominal F 65 90 52 65 76 67 72 70 70 74 81 76 Sound level 2 for guidance only Flue spigot outside diameter Total absorbed electrical power VCHE HCHE Model FRAME size I II III I...

Page 7: ...7 30 2 2 Dimensions Vertical heater range Figure 1a unit with discharge nozzle Front view Figure 1b unit with discharge plenum Front view...

Page 8: ...8 30 Figure 1c Side view Figure 1d Figure 1e Figure 1f burner mounting flange air inlet air inlet...

Page 9: ...e Figure 2a Side view Figure 2b Front view Remark The fixation eyes 4x dia 22 5 may only be used to put the unit into horizontal position after delivery It is strictly forbidden to use the fixation ey...

Page 10: ...3 2073 2012 2012 inside dia 1 burner inlet 110 110 120 120 140 140 155 155 155 155 H1 2088 2088 2168 2168 2376 2378 2477 2477 2466 2466 H2 2164 2164 2114 2114 2400 2400 2395 2395 2334 2334 K1 K2 35 5...

Page 11: ...appliance and in view when facing the service compartment The isolator must have a contact separation of at least 3 0mm on all poles 3 2 5 The cabinet heaters are foreseen with a control unit supplied...

Page 12: ...re in the zone as this will lead to a hazardous situation whereby the air heater flue will act as a pressure relief 3 3 6 Normally cabinet air heaters which are used in the free blowing mode i e witho...

Page 13: ...ake use of the fixation eyes to suspend the unit When unit is installed as a ducted heater the duct connections must be installed as described in 4 5 3 Ensure the dimensions of inlet outlet duct are t...

Page 14: ...sized in accordance with the diameter appropriate to the appliance flue connection socket Flues must be terminated with an approved terminal fitting Attention ensure that the connection of the flue t...

Page 15: ...for the sizes 140 150 180 and qty 18 for the sizes 215 250 see fig 8 The horizontal louvers may be adjusted to obtain proper deflection and air pattern For safety reasons it is recommended to wear glo...

Page 16: ...16 30 Figure 8 Nozzle plenum DB1 DA1 D A 2 D B 2 Figure 9 Vertical louvres...

Page 17: ...g Duct outlets must be adjusted when necessary to meet the values mentioned in table 9 Table 9 Frame Model Nominal airflow Available outlet static pressure Motor load maximum Motor current normal use...

Page 18: ...be adjusted when necessary to meet the values mentioned in table 9 4 5 5 Ducted air inlet on VCHE HCHE units The unit is designed so that it can be installed with inlet air ducts Vertical units Option...

Page 19: ...556 III 90 120 541 4 end 691 1054 651 1014 541 5 top 541 7 bottom 1201 707 1161 667 541 6 rear 1082 707 1042 667 IV 140 150 180 541 4 end 1082 1201 1042 1161 541 5 top 541 7 bottom 1400 596 1360 556 5...

Page 20: ...ails Filters must be inspected on a regular basis as dirty filters can affect the safe working of the unit For safety reasons it is recommended to wear gloves glasses when inspecting the filters Dirty...

Page 21: ...end 1 standard 2 duct left 3 duct right 4 duct rear Figure 13a Overview of the VCHE options Note When filters option 502 1 are required then the standard air intake panels must be replaced by the pane...

Page 22: ...before commencing then proceed with the following checks a Ensure electrical supply has been switched off b Ensure the gas supply is switched off c Check that the heater has been installed on a suita...

Page 23: ...Then check the following Fan limit stat settings are correct The bi metal strip has not been damaged The bi metal strip casing is not in contact with the heat exchanger body l Adjust temperatures and...

Page 24: ...Same as after 6 months b Heat exchanger inspection and cleaning c Burner maintenance d Main fan and motor e Pulley and belts f Flue system g Control panel and electrical connections h Gas supply conn...

Page 25: ...ave worn excessively then change the whole set immediately DO NOT MIX BELTS OF DIFFERENT AGES OR BATCHES As the belts stretch at a different rate according the batch curing number and age premature fa...

Page 26: ...sure switch Check gas pressure switch Check burner motor Burner starts but goes to lockout Check gas supply Bad earth Main gas cock open Air in gas line Flame probe failure Air pressure switch failure...

Page 27: ...ting Check control box Signal Check main gas actuator Burner lights but will not hold on main flame Insufficient air High inlet Pressure Fan limit stat Air inlets blocked Outlet nozzles closed Duct re...

Page 28: ...ustion chamber CC air deflector 10 fixation plate HE 11 sliding bracket HE 12 over pressure relief panel 13 heat exchanger combustion chamber 14 side air deflectors 15 side inner skins 16 top side pan...

Page 29: ...0 60 75 Contactor 60 61679 D910M5 sizes 90 120 140 150 180 215 Contactor 60 61679 D1210M size 250 60 61703 02 04 size 90 60 61703 04 06 size 120 60 61703 05 09 size 140 60 61703 07010 sizes 150 180 21...

Page 30: ...bility BSEN 50165 Safety of Electrical Equipment BS 5991 Indirect Gas Fired Heaters less than 2MW BS 5440 Part 1 Specification Installation of Flues Part2 Ventilation Requirements of Gas Appliances BS...

Reviews: