3
Get to Know Your Amazon
Identify Connections
USB
One mini-B and two USB-A connectors are provided, allowing direct connection to an external
device such as a Wi-Fi adaptor, laptop, tablet, or USB flash drive. USB flash drives can be used to
download data, save or load configuration files, and load firmware updates.
Power
The power input uses a 2 position connector; +12VDC and GND. The electronics and compressor power
is routed from this connection. NOTE : Because of the power requirments the Amazon should only be
powered from the sites main power source.
Ethernet
The Ethernet port is a 10/100 BaseT port allowing the Amazon to connect to a Local Area Network or a Wide Area
Network (Internet). The Ethernet is used for accessing the web interface or for modbus communication.
Communication
The communication port uses a 5 position connector; SDI-12 Data, RS-485 A, RS- 485 B, 4-20mA +, and 4-20mA -.
NOTE: When using SDI-12 remember the Amazon and data logger need a common ground.
Inlet
Air compressor intake desiccator connection
Outlet
Brass fitting 1/8 NPT to 3/8 tube for orifice line
Vent
Atmospheric pressure vent
I/O PANNEL CONNECTIONS