L17401-CL06JEN-E2-S02, REV. C INTRODUCTION TO TROUBLESHOOTING
Copyright © 2019 Amatrol, Inc.
S02-10
SKILL 2 TEST A MANUAL SWITCH
16. Perform the following substeps to test the upper set of contacts of selector
switch SS1 using the out-of-circuit test procedures.
A. Rotate the selector switch
SS1
operator to the center position.
In this position, the upper contacts of this switch should be open.
B. Place the multimeter leads into the terminals of the upper contacts of SS1,
as shown in fi gure 2-6, and record the measurement.
SS1 Resistance (operator in center) ______________________ (Ohms)
If the contacts are good, the resistance should be infi nite (open). This is
the fi rst step of testing the selector switch. The next step is to test it when
the operator is switched.
Figure 2-6. Selector Switch SS1 Contacts Test Method
COM
Ω
Ω
OPERATOR STATION
PN 17320
EARTH
GND
SS1
PB3
PB2
PB1