background image

4

C.

  

If the existing 

Indoor Coil Thermistor

 (with the 

RED

wires) was connected to the board by a plug-on
connector, reconnect it to the new board on the 

ICT

(red) terminals. If the previous board used indoor coil
bi-metals, remove and discard the bi-metal devices.
The access door will need to be removed on the indoor
coil to gain access to the bi-metal. See Figure 6. The
Indoor Coil Thermistor will need to clip on the vertical
section of the 90-degree bend of the inlet line to the
indoor coil. See Figure 7. Connect the Indoor Coil
Thermistor to the board as noted above.

D. If the existing 

Outdoor Coil Thermistor

 (with the

BLUE

 wires) was connected to the board by a plug-

on connector, reconnect it to the new board on the

OCT

 (blue) terminals. If the previous board used

indoor coil bi-metals, remove and discard the bi-metal
devices. The Indoor Coil Thermistor will need to clip on
the crossover tube shown in Figure 8.  There will be
two clips supplied in the kit for the Blue Thermistor.
One clip as supplied on the sensor will fit 5/16” tubing
used on the bent coil, and an additional clip (loose in
the bag) will fit 3/8” tubing used on the flat slab coil.
If you have a slab coil, you will need to remove the 5/16”
clip from the sensor and replace it with the 3/8” tube
clip. Connect the Outdoor Coil Thermistor to the board
as noted above. Outdoor Coil Thermistors are only
used on Heat Pump models; 

DO NOT INSTALL THIS

SENSOR IF THE UNIT IS NOT A HEAT PUMP.

Figure 7

INDOOR COIL THERMISTOR - RED

All Units

Connect to ICT on Control Board

Cross over tube
for 9,12 and 15k
or center tube for 
7,000 BTU 

Figure 8

17. If the unit has a condensate pump, go to step 18. If the unit

has a power vent or power door, go to step 19.  Otherwise
proceed with step 20.  Refer to wiring diagrams in back of
manual.

18.

Condensate Pump Units Only

(See Wiring Diagram Page 10

Reconnect the wires across the top terminals of the
control board.  Connect as follows:

Red 33 to Line 1

Brown 34 to Heater 1

Brown 34 to Heater 2

Power cord (or black 18) to Line 2

Violet 12 and Yellow 3 to Compressor

Black 16 to Fan High

Red 17 to Fan Low

19 from reversing valve and Yellow 1 to Rev. Valve.

Connect the yellow 5 wire to the 230 or 265-volt terminal
as applicable using the piggyback terminal on the yellow
5 wire. Go to step 21.

Summary of Contents for RSKP0006

Page 1: ...or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of specific good safety practices follow them T...

Page 2: ...ges Orient the control panel so there is easy access for mounting components to the inside of the control panel 11 Using the two 8 screws that are provided screw the transformer that was provided with the kit to the control panel in the transformer mounting holes provided in the panel See Figure 3 12 The external transformer will come with the Black 37 wiresconnectedtotheLOADterminalofthetransform...

Page 3: ...lluminated continu ously For status light functionality the YELLOW thermistor MUST be installed Instructions are as follows A1 Carefully cut and remove the gasket on the left and right sides of discharge screen Remove the two 2 5 16 screwsholdingtheindoorexhaustscreenabove the indoor coil Remove the indoor exhaust screen Removethetwo 2 1 4 screwsconnectingtheheater panel to the evaporator coil Rem...

Page 4: ...sed on the bent coil and an additional clip loose in the bag will fit 3 8 tubing used on the flat slab coil Ifyouhaveaslabcoil youwillneedtoremovethe5 16 clip from the sensor and replace it with the 3 8 tube clip ConnecttheOutdoorCoilThermistortotheboard as noted above Outdoor Coil Thermistors are only usedonHeatPumpmodels DONOTINSTALLTHIS SENSOR IF THE UNIT IS NOT A HEAT PUMP Figure 7 INDOOR COIL...

Page 5: ...in connector to low voltageterminalstrip If replacing a previous version board you will need to use the 18 pin connector supplied with the board for low voltage accessories Wires supplied with this kit have terminal ends on the wires Insert the terminal end into the correctly labeled slot push in and it will lock in place After loading pin connector use the wire nuts supplied with the kit to wire ...

Page 6: ...6 BLACK w WHITE STRIPE YELLOW w BLACK STRIPE RED GREEN WHITE YELLOW BLUE GREEN w YELLOW STRIPE Remote Thermostat BROWN Only load wires needed for accessories attached to unit Figure 9 ...

Page 7: ...E FAN LOW FAN HIGH LINE 1 ON 24VAC TRANSFORMER DSI IN GL GH B YELLOW Heat Pump models ONLY Must not be used on PTC models RIBBON CONNECTOR Left is ON Position YELLOW ORANGE from Touch Pad BLUE RED BLACK Figure 10 ...

Page 8: ...TAGE FOR A HEAT PUMP OFF 2 RIBBED WIRE MUST BE CONNECTED AS SHOWN ANTICIPATOR GN 1 R TO HEAT PUMP W AUXILIARY REMOTE THERMOSTAT OPERATION FAN PANEL W ELECTRIC HEAT CHASSIS R TO 2ND STAGE 1ST STAGE G Y W1 FACTORY OR FIELD FACTORY OR FIELD HEAT OFF 230 265 COM TRANSFORMER LOAD SOLENOID R SWITCH BK18 YL10 BR14 ELECTRIC GY22 C CAP H HEATER 4 1 DESK 2 F 19 WIRE RD17 RD13 BK16 S OD VALVE C G N RIBBED FA...

Page 9: ...ITCH ON OFF VT12 5 BK18 MO OR T 1 LINE CO M 208 240 FAN MUFFIN 20 HEATER ELECTRIC CAP FAN COMP OD WH15 BR14 19 SOLENOID VALVE 2 GN WIRE RIBBED H C F YL10 RD13 S C R R TO G Y W1 G B Y W1 G W2 FUNCTION OFF 1ST STAGE HEAT 2ND STAGE HEAT R TO G Y W1 FUNCTION OFF HEAT G FAN G FAN FOR A HEAT PUMP THERMOSTAT USED ON A STRAIGHT COOL UNIT GL low speed GH high speed W ELECTRIC HEAT COOLING UNIT ELECTRIC HEA...

Page 10: ... AND 115V TRANSFORMER NOT SHOWN 240 208 COM LINE OR8 CP 7 FOR REMOTE OPERATION SEE CONFIGURATION CHART 6 YL1 CP YL5 CP YL3 CP BK16 RD17 WH 6 CP HEAT PUMP W AUXILIARY ELECTRIC HEAT R TO G Y W1 G B Y W1 G W2 FUNCTION OFF COOL 1ST STAGE HEAT 2ND STAGE HEAT COOLING UNIT W ELECTRIC HEAT CONNECT R TO G Y W1 FUNCTION OFF REMOTE THERMOSTAT OPERATION HEAT G FAN G FAN FOR A HEAT PUMP THERMOSTAT USED ON A ST...

Page 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 12: ... product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality Visit our website at www amana ptac com for information on Products Warranties Customer Services Parts Contractor Programs and Training Financing Options 2006 Goodman Company L P is a ...

Reviews: