background image

12

Goodman Company, L.P.

2550 North Loop West, Suite 400

Houston, TX  77092

Quality Makes the Difference!

All of our systems are designed and manufactured with the same high quality standards regardless of size or
efficiency. We have designed these units to significantly reduce the most frequent causes of product failure.
They are simple to service and forgiving to operate. We use quality materials and components. Finally, every
unit is run tested before it leaves the factory. That’s why we know. . .

There’s No Better Quality.

Visit our website at 

www.amana-ptac.com

 for information on:

• Products
• Warranties
• Customer Services
• Parts
• Contractor Programs and Training
• Financing Options

©

 2006 Goodman Company, L.P.

®

is a trademark of Maytag Corporation and is used under

license to Goodman Company, L.P.  All rights reserved.

Summary of Contents for RSKP0006

Page 1: ...or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of specific good safety practices follow them T...

Page 2: ...ges Orient the control panel so there is easy access for mounting components to the inside of the control panel 11 Using the two 8 screws that are provided screw the transformer that was provided with the kit to the control panel in the transformer mounting holes provided in the panel See Figure 3 12 The external transformer will come with the Black 37 wiresconnectedtotheLOADterminalofthetransform...

Page 3: ...lluminated continu ously For status light functionality the YELLOW thermistor MUST be installed Instructions are as follows A1 Carefully cut and remove the gasket on the left and right sides of discharge screen Remove the two 2 5 16 screwsholdingtheindoorexhaustscreenabove the indoor coil Remove the indoor exhaust screen Removethetwo 2 1 4 screwsconnectingtheheater panel to the evaporator coil Rem...

Page 4: ...sed on the bent coil and an additional clip loose in the bag will fit 3 8 tubing used on the flat slab coil Ifyouhaveaslabcoil youwillneedtoremovethe5 16 clip from the sensor and replace it with the 3 8 tube clip ConnecttheOutdoorCoilThermistortotheboard as noted above Outdoor Coil Thermistors are only usedonHeatPumpmodels DONOTINSTALLTHIS SENSOR IF THE UNIT IS NOT A HEAT PUMP Figure 7 INDOOR COIL...

Page 5: ...in connector to low voltageterminalstrip If replacing a previous version board you will need to use the 18 pin connector supplied with the board for low voltage accessories Wires supplied with this kit have terminal ends on the wires Insert the terminal end into the correctly labeled slot push in and it will lock in place After loading pin connector use the wire nuts supplied with the kit to wire ...

Page 6: ...6 BLACK w WHITE STRIPE YELLOW w BLACK STRIPE RED GREEN WHITE YELLOW BLUE GREEN w YELLOW STRIPE Remote Thermostat BROWN Only load wires needed for accessories attached to unit Figure 9 ...

Page 7: ...E FAN LOW FAN HIGH LINE 1 ON 24VAC TRANSFORMER DSI IN GL GH B YELLOW Heat Pump models ONLY Must not be used on PTC models RIBBON CONNECTOR Left is ON Position YELLOW ORANGE from Touch Pad BLUE RED BLACK Figure 10 ...

Page 8: ...TAGE FOR A HEAT PUMP OFF 2 RIBBED WIRE MUST BE CONNECTED AS SHOWN ANTICIPATOR GN 1 R TO HEAT PUMP W AUXILIARY REMOTE THERMOSTAT OPERATION FAN PANEL W ELECTRIC HEAT CHASSIS R TO 2ND STAGE 1ST STAGE G Y W1 FACTORY OR FIELD FACTORY OR FIELD HEAT OFF 230 265 COM TRANSFORMER LOAD SOLENOID R SWITCH BK18 YL10 BR14 ELECTRIC GY22 C CAP H HEATER 4 1 DESK 2 F 19 WIRE RD17 RD13 BK16 S OD VALVE C G N RIBBED FA...

Page 9: ...ITCH ON OFF VT12 5 BK18 MO OR T 1 LINE CO M 208 240 FAN MUFFIN 20 HEATER ELECTRIC CAP FAN COMP OD WH15 BR14 19 SOLENOID VALVE 2 GN WIRE RIBBED H C F YL10 RD13 S C R R TO G Y W1 G B Y W1 G W2 FUNCTION OFF 1ST STAGE HEAT 2ND STAGE HEAT R TO G Y W1 FUNCTION OFF HEAT G FAN G FAN FOR A HEAT PUMP THERMOSTAT USED ON A STRAIGHT COOL UNIT GL low speed GH high speed W ELECTRIC HEAT COOLING UNIT ELECTRIC HEA...

Page 10: ... AND 115V TRANSFORMER NOT SHOWN 240 208 COM LINE OR8 CP 7 FOR REMOTE OPERATION SEE CONFIGURATION CHART 6 YL1 CP YL5 CP YL3 CP BK16 RD17 WH 6 CP HEAT PUMP W AUXILIARY ELECTRIC HEAT R TO G Y W1 G B Y W1 G W2 FUNCTION OFF COOL 1ST STAGE HEAT 2ND STAGE HEAT COOLING UNIT W ELECTRIC HEAT CONNECT R TO G Y W1 FUNCTION OFF REMOTE THERMOSTAT OPERATION HEAT G FAN G FAN FOR A HEAT PUMP THERMOSTAT USED ON A ST...

Page 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 12: ... product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality Visit our website at www amana ptac com for information on Products Warranties Customer Services Parts Contractor Programs and Training Financing Options 2006 Goodman Company L P is a ...

Reviews: