background image

2

3. Remove cabinet front from chassis by tilting the bottom of

the front forward, lifting slightly up and forward.

4. If a remote thermostat or any low voltage accessory is

being used, remove the low voltage pin connector from the
low voltage terminal strip. If a previous version board is
being replaced remove wires from the low voltage terminal
strip.

1

2

3

O

N

PULL TO REMOVE

THERMOSTAT KNOB

Lift Off

PULL TO REMOVE

MODE SWITCH KNOB

ESCUTCHEON

SCREW (2)

SCREW

Figure 2

5. Remove knobs and escutcheon.

6. Remove the two mounting screws, one on each side of

control board cover. Some models may have a screw on
the lower right side of the control panel that will need to be
removed. Tilt control panel out and remove cover.

7. Remove the wires from the board in the unit, including

Thermistor Sensors if they plug into the board.

8. Remove the four screws holding the board and remove the

old board.

New Control Board Installation Procedures

9. If existing unit has a remote mounted “off board” trans-

former for board power, proceed to Step 13.

10. Lift the control panel up so the control panel is free of its

hinges. Orient the control panel so there is easy access
for mounting components to the inside of the control
panel.

11. Using the two #8 screws that are provided, screw the

transformer that was provided with the kit to the control
panel in the transformer mounting holes provided in the
panel. See Figure 3.

12. The external transformer will come with the Black 37

wires connected to the LOAD terminal of the transformer
(LOAD terminals are the low voltage terminals) and the
Grey 22 wire connected to the COM terminal on the
transformer. The Grey 21 wire will need to be connected
to the 230 or 265 volt tap on the transformer. Place the
control panel back on its hinges.

NOTE: 

Refer to the serial plate for voltage information.

13. Install the new board and reinstall the screws removed in

step # 8.

14. Using the insulated terminals connect the two (2) Black

37 wires from the Load terminals on the transformer to the
“24VAC Transformer” terminals on the control board. See
Figure 4.

15.Connect Grey 22 wire from the COM terminal on the

transformer to line 2 on the control board.  Connect Grey
21 wire from the transformer to line 1 on the control board.

TRANSFORMER 

Figure 3

GY22

BK37

BK37

LINE 1

HEATER 1

HEATER 2

LINE 2

COMPRESSOR

2

4

V

A

C

~

T

RA

NS
F

O

RM

E

R

12V

A

 C
L

A

S

S

 2 O

N

LY

GY21

TRANSFORMER

LINE

LO

A

D

C

O

M

2

6

5

2

3

0

Figure 4

Summary of Contents for RSKP0006

Page 1: ...or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of specific good safety practices follow them T...

Page 2: ...ges Orient the control panel so there is easy access for mounting components to the inside of the control panel 11 Using the two 8 screws that are provided screw the transformer that was provided with the kit to the control panel in the transformer mounting holes provided in the panel See Figure 3 12 The external transformer will come with the Black 37 wiresconnectedtotheLOADterminalofthetransform...

Page 3: ...lluminated continu ously For status light functionality the YELLOW thermistor MUST be installed Instructions are as follows A1 Carefully cut and remove the gasket on the left and right sides of discharge screen Remove the two 2 5 16 screwsholdingtheindoorexhaustscreenabove the indoor coil Remove the indoor exhaust screen Removethetwo 2 1 4 screwsconnectingtheheater panel to the evaporator coil Rem...

Page 4: ...sed on the bent coil and an additional clip loose in the bag will fit 3 8 tubing used on the flat slab coil Ifyouhaveaslabcoil youwillneedtoremovethe5 16 clip from the sensor and replace it with the 3 8 tube clip ConnecttheOutdoorCoilThermistortotheboard as noted above Outdoor Coil Thermistors are only usedonHeatPumpmodels DONOTINSTALLTHIS SENSOR IF THE UNIT IS NOT A HEAT PUMP Figure 7 INDOOR COIL...

Page 5: ...in connector to low voltageterminalstrip If replacing a previous version board you will need to use the 18 pin connector supplied with the board for low voltage accessories Wires supplied with this kit have terminal ends on the wires Insert the terminal end into the correctly labeled slot push in and it will lock in place After loading pin connector use the wire nuts supplied with the kit to wire ...

Page 6: ...6 BLACK w WHITE STRIPE YELLOW w BLACK STRIPE RED GREEN WHITE YELLOW BLUE GREEN w YELLOW STRIPE Remote Thermostat BROWN Only load wires needed for accessories attached to unit Figure 9 ...

Page 7: ...E FAN LOW FAN HIGH LINE 1 ON 24VAC TRANSFORMER DSI IN GL GH B YELLOW Heat Pump models ONLY Must not be used on PTC models RIBBON CONNECTOR Left is ON Position YELLOW ORANGE from Touch Pad BLUE RED BLACK Figure 10 ...

Page 8: ...TAGE FOR A HEAT PUMP OFF 2 RIBBED WIRE MUST BE CONNECTED AS SHOWN ANTICIPATOR GN 1 R TO HEAT PUMP W AUXILIARY REMOTE THERMOSTAT OPERATION FAN PANEL W ELECTRIC HEAT CHASSIS R TO 2ND STAGE 1ST STAGE G Y W1 FACTORY OR FIELD FACTORY OR FIELD HEAT OFF 230 265 COM TRANSFORMER LOAD SOLENOID R SWITCH BK18 YL10 BR14 ELECTRIC GY22 C CAP H HEATER 4 1 DESK 2 F 19 WIRE RD17 RD13 BK16 S OD VALVE C G N RIBBED FA...

Page 9: ...ITCH ON OFF VT12 5 BK18 MO OR T 1 LINE CO M 208 240 FAN MUFFIN 20 HEATER ELECTRIC CAP FAN COMP OD WH15 BR14 19 SOLENOID VALVE 2 GN WIRE RIBBED H C F YL10 RD13 S C R R TO G Y W1 G B Y W1 G W2 FUNCTION OFF 1ST STAGE HEAT 2ND STAGE HEAT R TO G Y W1 FUNCTION OFF HEAT G FAN G FAN FOR A HEAT PUMP THERMOSTAT USED ON A STRAIGHT COOL UNIT GL low speed GH high speed W ELECTRIC HEAT COOLING UNIT ELECTRIC HEA...

Page 10: ... AND 115V TRANSFORMER NOT SHOWN 240 208 COM LINE OR8 CP 7 FOR REMOTE OPERATION SEE CONFIGURATION CHART 6 YL1 CP YL5 CP YL3 CP BK16 RD17 WH 6 CP HEAT PUMP W AUXILIARY ELECTRIC HEAT R TO G Y W1 G B Y W1 G W2 FUNCTION OFF COOL 1ST STAGE HEAT 2ND STAGE HEAT COOLING UNIT W ELECTRIC HEAT CONNECT R TO G Y W1 FUNCTION OFF REMOTE THERMOSTAT OPERATION HEAT G FAN G FAN FOR A HEAT PUMP THERMOSTAT USED ON A ST...

Page 11: ...11 THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 12: ... product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality Visit our website at www amana ptac com for information on Products Warranties Customer Services Parts Contractor Programs and Training Financing Options 2006 Goodman Company L P is a ...

Reviews: