ACCESSORY INSTALLATIONS
31
Hard Wire
Description
Hardwire Junction Box (Direct Wire Sub-Base)
The hardwire junction box kit is used to direct wire the unit
when it is not desirable to use the standard unit subbase or
the unit power cord. The junction box provides a protected
enclosure for electrical connections as required by some
electrical codes.
The hardwire junction box is intended to be mounted on the
floor or the adjacent wall.
The junction box is furnished with approximately 2-1/2 feet
of 1/2 inch flexible steel conduit and a metal box for secur-
ing the conduit to the unit cabinet at the incoming power
opening.
An optional 230/208V or 265V power switch assembly is
available for use with the hardwire junction box or subbase.
The switch provides a POWER ON/OFF function at the unit
as required by some electrical codes. A replacement junc-
tion box cover plate is provided with each switch kit. For
additional information, refer to the Power Switch Installation
Instructions.
Junction Box Kit Installation and Wiring Procedure
The installation and servicing of this equipment should be
performed by qualified, experienced technicians.
Electrical connections at the unit must be made after the
unit chassis is installed in the wall sleeve.
The installer must determine and supply the mounting com-
ponents for attaching the junction box to the wall or floor.
U
SE
COPPER
CONDUCTORS
ONLY
FOR
ELECTRICAL
CONNECTIONS
. T
HE
USE
OF
OTHER
TYPES
OF
CONDUCTORS
MAY
RESULT
IN
GAL
-
VANIC
CORROSION
,
OVERHEATING
AND
RESUL
-
TANT
EQUIPMENT
FAILURE
.
CAUTION
A
LL
WIRING
MUST
COMPLY
WITH
APPLICABLE
LOCAL
AND
NATIONAL
CODES
. T
YPE
AND
LOCATION
OF
FUSED
DISCONNECT
SWITCH
(
ES
)
MUST
COMPLY
WITH
ALL
APPLICABLE
CODES
.
F
AILURE
TO
FOLLOW
THESE
CODES
COULD
RESULT
IN
OVERHEATING
AND
EQUIPMENT
FAILURE
.
1. Remove the cover plate from the junction box.
2. Mount the junction box to the wall or floor within 28
inches of the lower right corner of the wall sleeve.
Wall Sleeve
Cover
Plate
Conduit
28 Inches Max
Metal Box
With Straight
Clamp
Power Leads
with Push
on Connectors
Ground Wire
With Eyelet
Terminal
Mounting Hardwire Junction Box Kit
3. If a disconnect switch is to be used, make electrical
connections to it and mount the switch in the junction
box. Refer to the “Power Switch” Installation Instruc-
tions.
4. Remove control panel assembly by removing the two
screws holding control panel in place. Rotate panel for-
ward.
5. Disconnect the power cord leads from all electrical con-
nections including the ground wire.
6. Remove the power cord clamp and the power cord from
the unit.
7. For 230/208-volt units, remove and discard the white
lead from the wire assembly. For 265-volt units, remove
and discard the red lead from the wire assembly.
8. Remove the retaining ring from the threaded portion of
the straight conduit clamp. Insert the three wires into
the metal box through one of the two openings in the
box. Replace the hole cover grommet into the unused
hole to prevent objects from entering the box.