Gas Connection Requirements
Before connecting this appliance to the gas supply piping
system, confirm that installation meets the requirements of
local codes, or in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1-Latest Edition. In
Canada installation must conform with local codes or the
current Natural Gas Installation Code CAN/CGA-B149.1.
Pressure Regulator Location
8-1/4"
11"
8-1/4"
CAUTION
Range designed for use with natural gas only.
Gas Supply Pressure
• The appliance and its individual shutoff valve must be
disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of ½ psig (3.5kPa)
(14" WCP).
• The appliance must be isolated from gas supply
piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
½ psig (3.5kPa) (14" WCP).
• Gas supply pressure for checking regulator setting
must be at least 1" WCP above manifold pressure
shown on rating label.
WARNING
To avoid property damage, maximum gas supply
pressure must not exceed 14" WCP.
Gas Supply Location
Gas supply must be located in the shaded area shown
below. Gas connection must not interfere with the
electrical connection.
2"
6"
4"
2"
2"
4"