4
installation.
ATTENTION: When fan is installed on GFCI (Ground Fault Circuit Interrupter) protective branch circuit, the fan
can be used under humid environment.
WARNING: This circuit is not suitable for persons (including children) with reduced physical, sensory or mental
capabilities or lack of relevant experience and knowledge, unless they have been given supervision or
instruction concerning use of the appliance in a safe way by those who are responsible for their safety.
Children should be supervised, in order to ensure they cannot play with appliance.
Please ATTENTION: If the fan is installed in the USA, installation must abide by the following guidance of National
Fire Protection Association (NFPA):
⚫
Fan must be located in the center of four (4) adjacent fire sprinklers.
⚫
The vertical distance between fan and flow deflector of fire sprinkler should be no less than 3
ft (91.4 cm).
⚫
Fan must be interlocked, it can immediately be turned off when receiving water flow signal
of alarm system.
WARNING: If fan abnormally swings, please immediately stop using overhead fan and contact manufacture,
maintenance agent or qualified personnel.
WARNING: Components of safety hanging system device should be replaced by manufacture, maintenance agent or
qualified personnel.
Installation of hanging system should be operated by authorized agent of brushless fan and corresponding qualified
personnel.
It is not suitable to be used in salt fog environment.
When finish installation, please leave this installation guide to fan user.