Ama Tech AH-5 Installation Manual Download Page 20

 

19 

 

Trouble Codes of Variable Frequency Drive: 

Code

 

Displayed Content 

on the Screen

 

Symptoms 

Solution 

ERROR 

 

1.

 

Power supply voltage is 

low 

2.

 

Reset function RES“on” 

3.

 

Operator loose contact 

with Main Machine   

4.

 

Trouble of internal circuit 

5.

 

CPU misoperation

 

1.

 

Supply with normal power

 

2.

 

Cut off reset switch

 

3.

 

Confirm to connect operator to 

Main Machine

 

4.

 

Replace variable frequency 

drive

 

5.

 

Restart variable frequency drive

 

OC0 

Over current during 

stopping machine

 

 

Output  current  exceed  2  times 
as  rated  current  of  variable 
frequency drive

 

Variable frequency drive may be 
interrupted, power off and re-power 
on, if this abnormal alarm happens 
repeatedly, please sent it to 
manufacture for inspecting and 
repairing

 

OC1 

Over current during 

acceleration

 

 

1.

 

If there is rapid acceleration or 
rapid deceleration, please 
extend time of acceleration and 
deceleration 

2.

 

Prevent load from rapidly 
enlarging 

3.

 

Check whether short circuit will 
happen on U/T1, V/T2 and 
W/T3 terminals of motor

 

OC2 

Over current during 

constant speed

 

 

OC3 

Over current during 

deceleration

 

 

OV0 

Over voltage 

during stopping 

machine

 

 

Voltage between terminal (+/P) 
and (-/N) is over high

 

Check whether input power is 
normal

 

OV1 

Over voltage during 

acceleration

 

 

1.

 

If there is rapid acceleration or 
rapid deceleration, please 
extend time of acceleration and 
deceleration 

2.

 

Check whether regenerative 
braking resistor between 
te/P and PR will fall

 

3.

 

Check whether the set value 
between 06-05(P.30) and 06-06 
(P.70) is correct

 

OV2 

Over voltage during 

constant speed

 

 

OV3 

Over voltage 

during deceleration

 

 

THT 

IGBT module is 

overheated

 

 

Thermal  relay  operation  of 
IGBT module

 

Prevent  variable  frequency  drive 
from long-time overload running

 

THN 

Motor is 

overheated

 

 

Electronic thermal relay 
operation

 

1.

 

Check whether set value of 
06-00(P.9) is correct (based on 
external motor) 

2.

 

Reduce load

 

OHT 

Operation of 

thermal relay of 

external motor

 

 

Thermal relay operation of 
external motor

 

1.

 

Check whether external thermal 
relay capacity match to motor 
capacity 

2.

 

Reduce load

 

OPT 

Peripheral 

abnormality

 

 

1.

 

Communication 
abnormality, exceed retry 
times of communication 
abnormality 

2.

 

Communication 
interruption, exceed 
allowable time of 
communication interval

 

1. 

Correctly  set  parameters  related 

to communication

 

Summary of Contents for AH-5

Page 1: ......

Page 2: ...1 Installation Guide Type Model to be installed Helicopter Fan AH 5 Helicopter Fan AH 6 Helicopter Fan AH 7...

Page 3: ...ation Structure Square Steel Beam Optional 11 1 Installation Structure Cement Beam Optional 12 1 Installation Structure Round Steel Beam Optional 13 2 Installing Main Machine Extension Fan Unit 14 3 I...

Page 4: ...to damaged or dangerous power supply Please do not try to solve circuit problem or trouble by yourself If you have any problem about installation of this fan please contact AmaTech WARNING For reducin...

Page 5: ...nce of National Fire Protection Association NFPA Fan must be located in the center of four 4 adjacent fire sprinklers The vertical distance between fan and flow deflector of fire sprinkler should be n...

Page 6: ...ad Current A 0 5 3 8A 0 46 2 8A 0 43 2 0A 3 Phase Voltage V 220 220 220 Max Affected Area m2 1300 1000 700 Wind Volume at Max Speed m3 min 14900 12400 10900 Noise Level dB 40 40 40 Fan Blade 5 5 5 Wei...

Page 7: ...n Unit 1 2 Fan Blades Box Fan Blade 5 3 Other Components Box Mounting Clamp 2 Universal Mount 1 Extension 1 Guy Wire Plate 2 Lamp Holder Plate 1 Lamp Holder 1 Airfoil 5 Galvanized Hex Bolt M12 60 4 pi...

Page 8: ...7 Pre Installation Components Inspection 2 3 Other Components Box 1 Mounting Clamp 2 Universal Mount 1 Extension 1 Guy Wire Plate 2 Water proof Cap 1 Winglet 5...

Page 9: ...M12 60 4 pieces M12 100 2 pieces Hex Socket Head Bolt M12 M12 100 2 pieces Hex Socket Head Bolt M12 M12 110 2 pieces Hex Bolt Nylok M12 60 10 pieces Self tapping Screw M4 M4 20 10 pieces Nylon Hex Lo...

Page 10: ...ce Installation Standard and Metric Wrench Kit Phillips Screwdriver and Flathead Screwdriver Standard and Metric Screw and Ratchet Kit 10 14 AWG Wire Stripper Standard and Metric General Wrench Kit Me...

Page 11: ...position position the Universal Mount under the I Beam assemble one Mounting Clamp with one side of the I Beam and then pre tighten them The above step will be repeated on the other side After finish...

Page 12: ...osition the Universal Mount under the Square Steel Beam assemble the Mounting Clamp with low edge of the Square Steel Beam and then pre tighten them and pre tighten all Hex Nuts on the Threaded Rods A...

Page 13: ...e L Type Bracket on the Cement Beam with the Expansion Bolts the above step will be repeated on the other side of Cement Beam bottoms of 2 L Type Bracket should be leveling Position the Universal Moun...

Page 14: ...allation position attach the Universal Mount under Round Steel Beam put U Type Fixing Rings on the Round Steel Beam and pre tighten them Pre tighten all nuts After finish apply loctite to all bolts th...

Page 15: ...Wire Plates on both sides then attach washers to outside of Guy Wire Plates insert Hex Socket Head Bolts tighten Hex Nuts to finish it torque to 60 NM Overhead operation 4 Stretch cable hose then thr...

Page 16: ...Tighten fan blades to airfoils with screws torque to 3 5 NM A Assemble them with fan unit by overhead operation B Avoid scratching surfaces of fan blades when installing fan blades apply loctite to a...

Page 17: ...s horizontal vertical and beautiful the distance between Cable Clamps is 1 5m Overhead and ground operation Attention Cables must be connected with same colors for example yellow green connect to yell...

Page 18: ...onnect cables to control system according to corresponding circuit colors 3 Use Multimeter to measure after finish turn on circuit breaker and power it on turn on fan for test counterclockwise rotatio...

Page 19: ...ame Grounding Terminal Notes There are no built in braking units in Frame A and no P and PR terminals Main Circuit Terminal Array of Various Machines Frame A Frame B Braking Resistor Connection Notes...

Page 20: ...current during deceleration OV0 Over voltage during stopping machine Voltage between terminal P and N is over high Check whether input power is normal OV1 Over voltage during acceleration 1 If there i...

Page 21: ...h 1 Reduce ambient temperature and improve ventilation condition 2 Confirm whether fan of variable frequency drive normally operates OL2 Over torque abnormality 1 Motor is overloaded 2 Setting of para...

Page 22: ...nt press power button 5 During fan running press power button again equipment will stop 6 When fan is running normally forbid to power off 7 After turn off fan and before the fan blades completely sto...

Page 23: ...1 2 Dead On Arrival DOA 1 2 1 Products shall be only confirmed as DOA when there are defects on arrival and trouble which is not caused by abnormal use of Products damage during freight or unauthorize...

Page 24: ...f equipment power when installing d This Product has been abused misused or incorrectly installed e Wrong wire connection f Products trouble caused by natural disasters or force majeure g Damage in fr...

Reviews: