background image

 

ReServV 

- 3 -

Installation Instructions:

This installation should be made by qualified service personnel and should conform to all local codes and in 
accordance with the 
National Electrical Code. Product is intended for indoor use only. This product contains no serviceable parts.
1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in 
  the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 
  enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two 
  holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper 
  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 
  (Enclosure Dimensions, pg. 8). Secure enclosure to earth ground. 
 

Note: This product needs to be secured to the building before operation.

2.  Connect AC power mains to the terminals marked [L] and [N]. Connect ground wire to ground lug 
  (Figs. 1-3, pg. 5-7).
  Use 18 AWG or larger for all power connections (Battery, output) (Figs. 1-3, pg. 5-7).
  Use 18 AWG to 22 AWG for supervision circuits (AC Fail/Low Battery reporting) (Figs. 1-3, pg. 5-7).
 

Note: A readily accessible disconnect device shall be incorporated in the building installation wiring.

3.  The LEDs on the power supply board will illuminate when AC power is present.
4.  Measure output voltage before connecting cameras/devices to outputs. This helps avoiding potential damage.
5.  ReServ3V only - Adjust voltage for every two (2) outputs using the corresponding trimpot(s) on the board 
  prior to connecting devices.
6.  Connecting cameras/devices:
 

ReServ1V -  Connect 12VDC cameras/devices to the terminals marked [P 1-4, N 1-4] (Fig. 1, pg. 5).

       

Connect 24VAC cameras/devices to the terminals marked [5-16] (Fig. 1, pg. 5).

 

ReServ2V -  Connect 24VAC cameras/devices to the terminals marked [1-16] (Fig. 2, pg. 6).

 

ReServ3V -  Connect 12VDC cameras/devices to the terminals marked [P 1-16, N 1-16] (Fig. 3, pg. 7).

7.  Connect batteries to the terminals marked [+ BAT –] (Figs. 1-3, pg. 5-7)
  Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included).
  Use batteries - Casil CA1270 (12V/7AH), Genesis NP7-12 (12V/7AH), Ultratech UT1270 (12V/7AH).
8.  Connect appropriate signaling notification devices to AC FAIL and BAT FAIL (Figs. 1-3, pg. 5-7)
  supervisory relay outputs.
9.  The power LEDs on the unit for Outputs 1-16 will illuminate when AC power is present (Figs. 1-3, pg. 5-7).  
 

Note: If any of the power LEDs are not illuminated, the cause may be due to the following:

  a.  AC mains and battery fail.
  b.  One (1) or more power output PTCs are tripped due to a short circuit or overload condition.
  c.  Unit damaged/defective.
    To reset the PTC:
    1.  Disconnect corresponding camera/device connected to terminals marked [1-16] (Figs. 1-3, pg. 5-7).
    2.  Eliminate the trouble condition (short circuit or overload).
    3.  Allow 1 minute for PTC to cool off (reset).
    4.  Connect corresponding cameras/devices to the terminals marked [1-16] (Figs. 1-3, pg. 5-7).
    5.  Power LEDs will illuminate indicating power has been restored to outputs (Figs. 1-3, pg. 5-7).

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or 
moisture. This installation should be made by qualified service personnel and should conform 
to the National Electrical Code and all local codes.

The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the 
user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that 
may be of sufficient magnitude to constitute an electric shock.

The exclamation point within an equilateral triangle is intended to alert the user to the presence of 
important operating and maintenance (servicing) instructions in the literature accompanying
the appliance.

CAUTION: To reduce the risk of electric shock do not open enclosure. 
There are no user serviceable parts inside. 
Refer servicing to qualified service personnel.

Summary of Contents for ReServ Series

Page 1: ... four 4 regulated 12VDC outputs 4A total supply current 24VAC and 2A total supply current 12VDC PTC protected power limited outputs ReServ2V Sixteen 16 true sine wave regulated 24VAC outputs 4A total supply current PTC protected power limited outputs ReServ3V Sixteen 16 regulated 12VDC outputs 8A total supply current PTC protected power limited outputs ...

Page 2: ...ails Supervision AC fail supervision form C contacts Low battery supervision form C contacts Visual Audio Indicators AC DC power LED indicators Individual power output LED indicators Low voltage input and Shutdown LED indicators Audio AC Fail and Battery Fail indicator Additional Features True sine wave regulated AC outputs ReServ1V ReServ2V Regulated DC outputs ReServ1V ReServ3V Unit maintains ca...

Page 3: ... to the terminals marked 1 16 Fig 2 pg 6 ReServ3V Connect 12VDC cameras devices to the terminals marked P 1 16 N 1 16 Fig 3 pg 7 7 Connect batteries to the terminals marked BAT Figs 1 3 pg 5 7 Use two 2 12VDC batteries connected in series for 24VDC operation battery leads included Use batteries Casil CA1270 12V 7AH Genesis NP7 12 12V 7AH Ultratech UT1270 12V 7AH 8 Connect appropriate signaling not...

Page 4: ... Terminal Identification Power Supply Board Terminal Legend Function Description L G N Connect 230VAC 50 60Hz to these terminals L to hot N to neutral DC 24VDC non power limited output AC FAIL NO C NC Form C dry contacts used to instantaneously signal the loss AC to local annunciation devices with AC present terminals marked NO and C are open NC and C are closed When loss of AC occurs terminals ma...

Page 5: ...ately 12VDC Rechargeable Battery order separately Supervised CAUTION Risk of explosion if battery is replaced by an incorrect type Dispose of used batteires according to the instructions 5A 250V Unswitched 230VAC 50Hz 2A power mains 24VAC Outputs 12VDC Outputs Note Two 2 12VDC rechargeable batteries connected in series required Ground Lug ...

Page 6: ...er separately 12VDC Rechargeable Battery order separately Supervised CAUTION Risk of explosion if battery is replaced by an incorrect type Dispose of used batteires according to the instructions 5A 250V Unswitched 230VAC 50Hz 2A power mains Note Two 2 12VDC rechargeable batteries connected in series required 24VAC Outputs Ground Lug ...

Page 7: ...laced by an incorrect type Dispose of used batteires according to the instructions 5A 250V Unswitched 230VAC 50Hz 2A power mains Note Two 2 12VDC rechargeable batteries connected in series required 12VDC Outputs P N 3 OUT 4 3 4V adjust P N 5 OUT 6 5 6V adjust P N 7 OUT 8 7 8V adjust P N 9 OUT 10 9 10V adjust P N 11 OUT 12 11 12V adjust P N 13 OUT 14 13 14V adjust P N 15 OUT 16 15 16V adjust Ground...

Page 8: ...e in U S A IIReServV E25R MEMBER Enclosure Dimensions H x W x D approximate 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm ...

Reviews: