ReServV

LED Diagnostics:

Power Supply Board

Red (DC)

Green (AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

ReServ Board

LED

LED State

Unit Status

Output LEDs

ON

Normal operating condition.

OFF Loss of 24VAC and/or 12VDC output power.

Low Battery

ON

Stand-by batteries are low.

OFF Normal operating condition.

Shutdown

ON

Loss of 24VAC and/or 12VDC output power. Discharged stand-by battery.

OFF Normal operating condition.

Audio Signal Diagnostics:

ReServ Unit

Audio Signal

Unit Status

Single Periodic Beep

AC Fail.

Double Periodic Beep

Low Battery or No Battery.

Terminal Identification:

Power Supply Board

Terminal
Legend

Function/Description

L, G, N

Connect 230VAC, 50/60Hz to these terminals: L to hot, N to neutral.

– DC +

24VDC non power-limited output. 

AC FAIL 
NO, C, NC

Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation 
devices, with AC present terminals marked NO and C are open, NC and C are closed. 
When loss of AC occurs terminals marked NO and C are closed, NC and C are open.

BAT FAIL 
NO, C, NC

Form “C” dry contacts used to signal low battery voltage or loss of battery voltage. 
Under normal conditions terminals marked NO and C are open, NC and C are closed. 
During a trouble condition terminals marked NO and C are closed, and NC and C are open.

+ BAT –

Stand-by battery connections. Maximum charge current 0.7A.

ReServ Board

Terminal
Legend

Function/Description

Input
– 24VDC +

24VDC input from power supply board.

N, P 1-16

24VAC and/or 12VDC outputs. 

Summary of Contents for ReServ Series

Page 1: ... four 4 regulated 12VDC outputs 4A total supply current 24VAC and 2A total supply current 12VDC PTC protected power limited outputs ReServ2V Sixteen 16 true sine wave regulated 24VAC outputs 4A total supply current PTC protected power limited outputs ReServ3V Sixteen 16 regulated 12VDC outputs 8A total supply current PTC protected power limited outputs ...

Page 2: ...ails Supervision AC fail supervision form C contacts Low battery supervision form C contacts Visual Audio Indicators AC DC power LED indicators Individual power output LED indicators Low voltage input and Shutdown LED indicators Audio AC Fail and Battery Fail indicator Additional Features True sine wave regulated AC outputs ReServ1V ReServ2V Regulated DC outputs ReServ1V ReServ3V Unit maintains ca...

Page 3: ... to the terminals marked 1 16 Fig 2 pg 6 ReServ3V Connect 12VDC cameras devices to the terminals marked P 1 16 N 1 16 Fig 3 pg 7 7 Connect batteries to the terminals marked BAT Figs 1 3 pg 5 7 Use two 2 12VDC batteries connected in series for 24VDC operation battery leads included Use batteries Casil CA1270 12V 7AH Genesis NP7 12 12V 7AH Ultratech UT1270 12V 7AH 8 Connect appropriate signaling not...

Page 4: ... Terminal Identification Power Supply Board Terminal Legend Function Description L G N Connect 230VAC 50 60Hz to these terminals L to hot N to neutral DC 24VDC non power limited output AC FAIL NO C NC Form C dry contacts used to instantaneously signal the loss AC to local annunciation devices with AC present terminals marked NO and C are open NC and C are closed When loss of AC occurs terminals ma...

Page 5: ...ately 12VDC Rechargeable Battery order separately Supervised CAUTION Risk of explosion if battery is replaced by an incorrect type Dispose of used batteires according to the instructions 5A 250V Unswitched 230VAC 50Hz 2A power mains 24VAC Outputs 12VDC Outputs Note Two 2 12VDC rechargeable batteries connected in series required Ground Lug ...

Page 6: ...er separately 12VDC Rechargeable Battery order separately Supervised CAUTION Risk of explosion if battery is replaced by an incorrect type Dispose of used batteires according to the instructions 5A 250V Unswitched 230VAC 50Hz 2A power mains Note Two 2 12VDC rechargeable batteries connected in series required 24VAC Outputs Ground Lug ...

Page 7: ...laced by an incorrect type Dispose of used batteires according to the instructions 5A 250V Unswitched 230VAC 50Hz 2A power mains Note Two 2 12VDC rechargeable batteries connected in series required 12VDC Outputs P N 3 OUT 4 3 4V adjust P N 5 OUT 6 5 6V adjust P N 7 OUT 8 7 8V adjust P N 9 OUT 10 9 10V adjust P N 11 OUT 12 11 12V adjust P N 13 OUT 14 13 14V adjust P N 15 OUT 16 15 16V adjust Ground...

Page 8: ...e in U S A IIReServV E25R MEMBER Enclosure Dimensions H x W x D approximate 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm ...

Reviews: