MaxiFit11E/13E/33E/35E/37E/55E/75E/77E Expandable Power Systems Installation Guide 

- 6 -

Power Supply Board Stand-by Battery Specifications

Altronix

Model

Power Supply

Board

Battery

20 min. of

Backup

4 hr. of

Backup

24 hr. of

Backup

60 hr. of

Backup

MaxFit11E

MaxFit13E

AL400ULXB2

(Refer to Fig. 2a on 

pg. 4 for 

Switch [SW1] 

location and 

position)

12VDC/40AH*

N/A

4A

1A

300mA

24VDC/12AH

N/A

200mA

N/A

N/A

24VDC/40AH*

N/A

3A

1A

300mA

MaxFit13E

MaxFit33E

MaxFit35E

MaxFit37E

AL600ULXB

(Refer to Fig. 2a, 

on pg. 4 for 

Switch [SW1] 

location

and position)

12VDC/40AH*

N/A

6A

1A

300mA

24VDC/12AH

N/A

200mA

N/A

N/A

24VDC/40AH*

N/A

6A

1A

300mA

MaxFit35E

MaxFit55E

MaxFit75E

AL1012ULXB

(Factory set at 

12VDC)

12VDC/12AH

10A

Battery capacity 

for emergency 

stand-by at least 

20 mins.

N/A

N/A

MaxFit37E

MaxFit75E

MaxFit77E

AL1024ULXB2

(Factory set at 

24VDC)

24VDC/12AH

8A

1.5A

200mA

100mA

24VDC/65AH*

N/A

8A

1.5A

500mA

* Note:

 Additional battery enclosure required (Fig. 3, pg. 7).

Summary of Contents for MAXIMAL FIT MaxFit E Series

Page 1: ...VDC 4A or 24VDC 3A Power Supply 2 12VDC 4A or 24VDC 3A MaxFit13E Power Supply 1 12VDC or 24VDC 6A Power Supply 2 12VDC 4A or 24VDC 3A MaxFit33E Power Supply 1 12VDC or 24VDC 6A Power Supply 2 12VDC or...

Page 2: ...12VDC 6A 12VDC 6A 12VDC 6A 24VDC 6A 24VDC 6A 24VDC 6A MaxFit35E AL1012ULXB AL600ULXB 2 6 1A 5A 250V 15A 32V AL1012ULXB 12VDC 10A 12VDC 6A 12VDC 10A 24VDC 6A MaxFit37E AL1024ULXB2 AL600ULXB 2 7 9A 5A...

Page 3: ...ls marked L N Fig 1a pg 5 Use 14 AWG or larger for all power connections Secure green wire lead to earth ground For Fire Alarm applications the outputs are Special Applications only Keep power limited...

Page 4: ...Test Under normal load conditions check that the battery is fully charged check specified voltage at the battery terminals and at the board terminals marked BAT to ensure that there is no break in the...

Page 5: ...rt pg 2 AC FAIL NO C NC Used to notify loss of AC power e g connect to audible device or alarm panel Relay normally energized when AC power is present Contact rating 1A 28VDC AC or brownout fail is re...

Page 6: ...C 12AH N A 200mA N A N A 24VDC 40AH N A 3A 1A 300mA MaxFit13E MaxFit33E MaxFit35E MaxFit37E AL600ULXB Refer to Fig 2a on pg 4 for Switch SW1 location and position 12VDC 40AH N A 6A 1A 300mA 24VDC 12AH...

Page 7: ...tWaySP3B NetWay4EB NetWaySP4B NetWaySP8B Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries are required for ULC S319 installations CAUTION When power supply board is set...

Page 8: ...8mm 8 75 222 3mm 8 75 222 3mm 1 50 38 1mm 1 50 38 1mm 6 25 158 8mm 1 25 31 8mm 1 25 31 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 1 25 31 8mm 1 25 31 8mm 16 50 419 1mm 1 25 31 8mm 0 75 1...

Reviews: