MaxiFit11E/13E/33E/35E/37E/55E/75E/77E Expandable Power Systems Installation Guide

NEC Power-Limited Wiring Requirements:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit 

wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited 

circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One 

such example of this is shown below. Your specific application may require different conduit

knockouts to be used. Any conduit knockouts may be used. For power-limited

applications use of conduit is optional. All field wiring connections must be made

employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). 

Optional battery enclosure must be mounted adjacent to the power supply via Class 1

wiring methods. For Canadian installations use shielded wiring for all connections.

Note: Refer to wire handling drawing below for the proper way to install the

CM or FPL jacketed wire 

(Fig. 3b)

.

Fig. 3

A ACM8(CB), ACMS8(CB),

LINQ8ACM

B

ACM4(CB), LINQ8PD(CB),

PD4UL(CB), PD8UL(CB),

MOM5, PDS8(CB), VR6

C PD16W(CB)

D NetWaySP3B, NetWay4EB,

NetWaySP4B, NetWaySP8B 

Optional

Rechargeable

Stand-by Battery

for UL294

Applications

  

Note:

12V batteries

are required for

ULC-S319

installations.

 

 

  CAUTION: When power supply board is set for 12VDC use

  only one (1) 12VDC stand-by battery. 

  Connect red battery lead to the terminal marked [+ BAT] and to

  the [positive (+)] terminal of the battery. 

  Connect black battery lead to terminal   marked [BAT –] and to

  the [negative (–)] terminal of the battery.

Keep power-limited wiring separate from non power-limited. 

  Use minimum 0.25" spacing.

  12AH Rechargeable batteries are the largest batteries that

  can fit in this enclosure. 

  An external battery enclosure must be

  used if using the 40AH or 65AH batteries.

Input 115VAC, 60Hz

(non power-limited)

Supervisory Connections (power-limited)

A

B

C

D

A

B

C

DC Output

(non power-limited)

Battery

(non power-limited)

DC Output

(non power-limited)

Battery

(non power-limited)

Tamper Switch

Power

Supply/

Charger

BAT FAIL NC  C  NO  NC  C  NO 

 AC  FAIL

AC

DC

BAT

+BAT-

+ DC -

L     G      

N

OFF - 24V

ON - 12V

ON

Power

Supply/

Charger

BAT FAIL NC  C  NO  NC  C  NO 

 AC  FAIL

AC

DC

BAT

+BAT-

+ DC -

L     G      

N

OFF - 24V

ON - 12V

ON

Fig. 3a

Tamper Switch

(included)

To Access Control Panel or

UL Listed Reporting Device

Edge of

Enclosure

Enclosure

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

Fig. 3b

Summary of Contents for MAXIMAL FIT MaxFit E Series

Page 1: ...VDC 4A or 24VDC 3A Power Supply 2 12VDC 4A or 24VDC 3A MaxFit13E Power Supply 1 12VDC or 24VDC 6A Power Supply 2 12VDC 4A or 24VDC 3A MaxFit33E Power Supply 1 12VDC or 24VDC 6A Power Supply 2 12VDC or...

Page 2: ...12VDC 6A 12VDC 6A 12VDC 6A 24VDC 6A 24VDC 6A 24VDC 6A MaxFit35E AL1012ULXB AL600ULXB 2 6 1A 5A 250V 15A 32V AL1012ULXB 12VDC 10A 12VDC 6A 12VDC 10A 24VDC 6A MaxFit37E AL1024ULXB2 AL600ULXB 2 7 9A 5A...

Page 3: ...ls marked L N Fig 1a pg 5 Use 14 AWG or larger for all power connections Secure green wire lead to earth ground For Fire Alarm applications the outputs are Special Applications only Keep power limited...

Page 4: ...Test Under normal load conditions check that the battery is fully charged check specified voltage at the battery terminals and at the board terminals marked BAT to ensure that there is no break in the...

Page 5: ...rt pg 2 AC FAIL NO C NC Used to notify loss of AC power e g connect to audible device or alarm panel Relay normally energized when AC power is present Contact rating 1A 28VDC AC or brownout fail is re...

Page 6: ...C 12AH N A 200mA N A N A 24VDC 40AH N A 3A 1A 300mA MaxFit13E MaxFit33E MaxFit35E MaxFit37E AL600ULXB Refer to Fig 2a on pg 4 for Switch SW1 location and position 12VDC 40AH N A 6A 1A 300mA 24VDC 12AH...

Page 7: ...tWaySP3B NetWay4EB NetWaySP4B NetWaySP8B Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries are required for ULC S319 installations CAUTION When power supply board is set...

Page 8: ...8mm 8 75 222 3mm 8 75 222 3mm 1 50 38 1mm 1 50 38 1mm 6 25 158 8mm 1 25 31 8mm 1 25 31 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 1 25 31 8mm 1 25 31 8mm 16 50 419 1mm 1 25 31 8mm 0 75 1...

Reviews: