eFlow3N Series Installation Guide

6.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

 

in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel 

 

type. Connect battery to terminals marked [– BAT +] 

(Fig. 1g, pg. 5)

. Use two (2) 12VDC batteries 

 

connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), 

 

CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 

 

batteries of an appropriate rating.

7.  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL 

(Fig. 1b, pg. 5)

 supervisory

 

relay outputs.

8.  To delay AC reporting for 2 hrs. set DIP switch [AC Delay] to OFF position 

(Fig. 1c, pg. 5)

.

 

To delay AC reporting for 1 min. set DIP switch [AC Delay] to ON position 

(Fig. 1c, pg. 5)

.

 

Note: 

Must be set to ON position for Burglar Alarm Applications.

9.  To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position 

(Fig. 1c, pg. 5)

.

 

To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position 

(Fig. 1c, pg. 5)

.

10.  Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals 

 

will cause [DC] output to shutdown 

(Fig. 1d, pg. 5)

.

11.  Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching

 

[Trigger EOL Shutdown] 

(Fig. 1e, pg. 5)

.

12.  For Access Control Applications: mount UL Listed tamper switch (Altronix Model TS112 or equivalent) at 

 

the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right 

 side 

(Fig. 4, pg. 7 or Fig. 6, pg. 9)

. Connect tamper switch wiring to the Access Control Panel input or the 

 

appropriate UL Listed reporting device.

Wiring:

Use 18 AWG or larger for all low voltage power connections.

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 Under normal load conditions, the DC output voltage should be checked for proper 

 

 

 

voltage level eFlow3N: 12VDC or 24VDC nominal rated @ 2A max.

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check specified 

 

 

 

voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at battery terminal and at the board 

 

 

 

terminals marked [– BAT +] to ensure that there is no break in the battery connection wires.

Note:

 Maximum charging current under discharges is 1.54A.

Note:

 Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Power Supply/Charger

Red (DC)

Green (AC/AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green (AC)

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Summary of Contents for eFlow3N

Page 1: ...4 2A 12VDC or 24VDC Four 4 Class 2 Power Limited Fused Outputs eFlow3N4D eFlow3NX4D 2A 12VDC or 24VDC Four 4 Class 2 Power Limited PTC Outputs Installation Guide Rev 3NRP013019 More than just power TM...

Page 2: ...4 2A P eFlow3NX4D 2A P These units are classified as Power Limited stand alone power supplies with stand by battery and they are suitable to power sensors electro mechanical devices e g electric door...

Page 3: ...fer to Appendix A pg 13 4 Measure output voltage before connecting devices This helps avoiding potential damage 5 Connect devices to be powered a For eFlow3N eFlow3NX connect devices to terminals mark...

Page 4: ...or Access Control Applications mount UL Listed tamper switch Altronix Model TS112 or equivalent at the top of the enclosure Slide tamper switch bracket onto the edge or the enclosure approx 2 from the...

Page 5: ...is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maximum ch...

Page 6: ...inals marked BAT FAIL C NO Fig 2 pg 6 NC C NO NC C NO BAT FAIL AC FAIL POWER SOURCE RED INDICATING LAMP Power Distribution Module s Fig 3a PD4UL Power Distribution Board Fig 3b PD4ULCB Power Distribut...

Page 7: ...e required for UL603 UL1481 and Canadian installations Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION...

Page 8: ...nal All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power suppl...

Page 9: ...ble Stand by Battery for UL294 Applications Note 12V batteries required for ULC S319 installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power lim...

Page 10: ...ional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power sup...

Page 11: ...6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 1...

Page 12: ...1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9m...

Page 13: ...24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50...

Page 14: ...mote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Page 15: ...ltronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warra...

Page 16: ...2A Over 4 Hours 2A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer to stand by...

Reviews: